RECEPTACLE REQUIRED PLUG PART NO.
15-50P
480 VOLTS, 50A
3908
14-60P
208/240 VOLTS, 60A
3909
SCHEMATIC DIAGRAMS
LR30 SERIES, A25 SERIES, A30 SERIES
EXCI TER
CAPACITOR
T5
T8
120V
T1
T2
T3
T4
MAIN PHASE
EXCI TER
CAPACITOR (S)
T5
T8
240V
T1
T2
T3
T4
MAIN PHASE
LR50 SERIES, LR55 SERIES, LR60 SERIES, LR70 SERIES,
LR80 SERIES, LR105 SERIES, LR150 SERIES, LR180 SERIES
A50/55/60 SERIES, LA50/55/60 SERIES
120V
120V
ELECTRIC MOTOR CHART
Approximate current requirements
HORSE-
POWER
RUNNING
WATTS
STARTING WATTS
UNIVERSAL
MOTOR
(sm. appliance)
INDUCTION
MOTOR
CAPACITOR
MOTOR
SPLIT
PHASE
MOTOR
1/6 275 400 600 850 1200
1/4 400 500 850 1050 1700
1/3 450 600 950 1350 1950
1/2 600 750 1300 1800 2600
3/4 850 1000 1900 2600 X
1 1000 1250 2300 3000 X
1 1/2 1600 1750 3200 4200 X
2 2000 2350 3900 5100 X
3 3000 X 5200 6800 X
5 4800 X 7500 9800 X
NOTE: For pumps, air compressors, air conditioners, inverters add
at least 25% to starting current.
EXTENSION CORD CHART
CONTINUOUS LOAD
(use either Amps or Watts below)
MINIMUM GAUGE (AWG)
AMPS
WATTS
@120 volts @240 volts 0-50 feet 50-100 feet 100-150 feet
2 240 480 22 20 18
3 360 720 22 18 16
4 480 960 20 16 16
5 600 1200 18 16 14
6 720 1440 18 16 14
8 960 1920 16 14 12
10 1200 2400 16 12 12
12 1440 2880 16 12 10
14 1680 3660 14 12 10
16 1920 3840 14 10 10
18 2160 4320 14 10 8
20 2400 4800 12 10 8
22 2640 5280 12 10 8
25 3000 6000 12 10 6
30 3600 7200 10 8 6
35 4200 8400 10 8 4
40 4800 9600 8 6 2
50 6000 12000 6 4 2
60 7200 14400 4 2
THREE PHASE OPERATION
All three phase generators operate similarly as single phase units.
Please note that when checking the no load voltage on any three
phase generator, the voltage will be about 10% below nameplate
rating. When a load is placed on the three phase generator, the
reactor transformer inside the generator activates and the voltage
immediately increases to the proper rated voltage of the three phase
generator. If an optional automatic voltage regulator is installed the
voltage regulation is +/- 1½%. The automatic voltage regulator is
required if relays, electric controls, etc. are used with a 3-phase motor.
A three phase plug is included with each unit.
When applying load to the generator, if the electric motor runs in
reverse direction than the motor is supposed to operate, you must stop
the generator, remove the electric load from the generator and then
reverse two of the electric motor leads on the terminal strip of the
motor. Restart the generator, apply the electric motor load and the
direction of the electric motor should be operating properly.
On all three phase generators there is a three phase circuit breaker
rated to the amperage load of each unit. If the circuit breaker trips
under load, you must remove some of the load to prevent over loading
the generator. All three phase circuit breakers are designed for motor
load starting permitting momentary over load conditions associated
with three phase motors.
NATIONAL ELECTRICAL CODE, ALL STATE AND LOCAL CODES.
IN CANADA, ALL CONNECTIONS MUST CONFORM TO CSA AND
HYDRO REQUIREMENTS. CONSULT A LICENSED ELECTRICIAN.
THE ILLUSTRATION TO THE SIDE ASSUMES 120/240 VOLT
SINGLE PHASE ELECTRIC SERVICE IS BEING SUPPLIED BY THE
UTILITY.
SINGLE PHASE
THE FORMULA FOR WATTAGE IS:
VOLTS X AMPERAGE = WATTAGE
EXAMPLE: 120(VOLTS X 10(AMPS) = 1200 (WATTS)
THREE PHASE
THE FORMULA FOR WATTAGE IS:
VOLTS X AMPERAGE X 1.732 X POWER FACTOR(USUALLY .8) = WATTAGE
VOLTS X AMPERAGE X 1.732 X = VOLT AMPERAGE