Owner`s manual
Owner’s Manual 27
Voltmaster Engine-Driven Generators
e. Start the engine using the electric starter or recoil cord,
referring to engine manufacturer’s instructions if necessary.
f. When the engine starts, close the choke.
g. For SG-Series models, ensure the green light is lit on the
ground-fault sensing module on the control panel.
3. Apply loads:
a. Before connecting any load to the generator, run the engine
for 2 to 3 minutes, allowing it to reach normal operating
temperature.
b. Apply loads by inserting plugs into the proper receptacles and
turning on connected equipment.
c. See Section 3.2.4 for details about applying loads.
3.2.7 Stopping the generator
Gradually remove all loads from the generator before stopping the
generator engine.
To stop the engine:
■ On models with an electric starter, rotate the key to the off position.
■ On all diesel models you must keep pressure on the stop lever until
the engine comes to a complete stop.
■ On model LR50EL and LR60EL generators without a battery, move
the red or black lever near the fuel tank to the down position.
■ On other models, move the start/stop switch on the engine to the
stop position.
Always wait for the engine to come to a complete stop.
Runaway diesel engine
If the diesel engine does not stop when the start/stop switch is
moved to the stop position, the oil in the engine sump has been
overfilled and the engine is using over pressurized sump oil as fuel.
To stop the engine with this condition you must block the air intake
flow until the engine stops.
If this situation has occurred, the air filter will be saturated with oil
and must be replaced before restarting the engine.