User Guide
On/Off
When the TIC 300 PRO is
activated, the blue LED and
audible alert will pulse at a slow
rate, approximately twice per
second.
Self-test
The TEST button should be used
to ensure tool is operational. The
TEST function will cause the blue
LEDs and audible alert to pulse at
a continuous rate on either LOW or
HIGH range setting.
TIC 300 PRO with VolTect
™
Quick Start Guide
Voltage
(Phase to ground)
Detection Distance
Average
1.5 kV 1’ 2”
2.0 kV 2’ 5”
4.0 kV 3”
10.0 kV 6’ 3”
25.0 kV 9’ 4”
50.0 kV 13’ 0”
75.0 kV 14’ 8”
100.0 kV 19’ 8”
122.0 kV 22’ 0”
Voltage
(Phase to Ground)
Detection Distance
(from energized line)
Average
30 V 1.5”
75 V 6.5”
100 V 8.5”
120 V 10”
220 V 1’1”
500 V 1’7”
1000 V 2’10”
1500 V 7’9”
For complete information on the TIC 300 PRO, visit amprobe.com
High Range SettingLow Range Setting
Shotgun adapter
for hot stick
attachment
High range
1,500 V to 122k V ac
LED lights
Low range
30 V to 1,500 V ac
Self-test
MSHA
United States Department of Labor
Mine Safety and Health Administration
LOW Range Setting
1. Push ON/OFF button to turn
the unit ON. The unit will
default to the high voltage
setting when powered-up.
2. Push the LOW range button,
and the unit is ready for low
voltage detection.
3. Place the probe tip near,
but not touching, the low
(<1000 V) voltage source. See
bottom table for range details.
4. If voltage is present, the blue
LEDs and audible alert will
pulse at an increased rate.
HIGH Range Setting
(> 1500 V and <122 kV)
(Must use with TIC 410A Hot
Stick Attachment)
1. Push ON/OFF button to turn
the unit ON. The unit will
default to the high voltage
setting when powered-up.
2. Approach the probe tip near,
but not touching, the high
voltage conductor. See bottom
table for range details.
3. If voltage is present, the blue
LEDs and audible alert will
pulse at an increased rate.
TIC 410A
Hot Stick
Attachment
TIC 300 PRO