b)  Current measurement „A“
   Never exceed the maximum permissible input values. Do not touch any 
circuitry or connection points when voltages exceeding 33 V/ACrms or 70 V/
DC might be applied. Risk of fatal injury!
   The maximum permissible voltage in the circuit against ground potential may 
not exceed 1000 V in CAT II or 600 V in CAT III.
   For your own safety, observe all relevant safety instructions, regulations and 
safety measures.
The multimeter features a folding current clamp (2) for non-contact current measurement. 
Thesensorsintheclampdetectthemagneticeldsurroundedbytheliveconductors.
Measurement of insulated as well as non-insulated conductors and rails is permissible. 
Make sure that the conductor always passes through the middle of the clamp (observe arrow 
markings).
   Only ever clamp one cable at a time. If you clamp the supply and return conductors 
(i.e. L and N or positive and negative), the currents will cancel one another out and you 
will not get a measurement. If you clamp more than one outer cable (i.e. L1 and L2 or 
positive conductor 1 and positive conductor 2), the currents will add up.
   A cable selector (1) is located at the tip of the clamp so you 
can conveniently isolate and clamp individual conductors 
from a cable harness.
   In case of low currents, you may coil a conductor around 
one arm of the clamp several times. Then divide the 
measuring result by the number of coils to receive the 
correct current value.