-   Turn on the DMM using the rotary switch (13) and select the measuring range „A 
„. The 
display shows „A“ and the symbol for alternating current „
„.
-   In the alternating current measuring range, the 
display is set to zero automatically when the 
clamp is closed. If a strong magnetic eld in 
the vicinity is affecting the display, you can 
compensate this undesired display value using 
the REL function (relative value measure-
ment).
-   Push the open lever (4) to open the current 
clamp.
-   Clamp the individual conductor to be 
measured and reclose the clamp. Position the 
conductor in the middle of the two triangular 
position symbols on the clamp.
-   The alternating current is shown in the large 
display, the frequency in the small display above it.
-   Remove the clamp from the measuring object and turn off the device after measurement. 
Turn the rotary switch to „OFF“.