b) Opening/closing the exible current sensor
Applying and removing the current clamp to or from non-isolated, dangerously live conductors is not
permitted.
Thepowercircuitmustbeofzero-voltagestatebeforeapplyingorremovingtheexiblesensor.
Use personal protective equipment.
• Inordertoopentheexiblecurrentsensor(5),
rstturntherotarylock(6)anticlockwiseby90º.
• Pulltheendoftheexiblecurrentsensorout
from the rotary lock.
• Embrace the conductor to be measured with the
exiblesensorandthenguideitbackintothe
rotary lock.
• Turn the rotary lock clockwise by 90º. The arrow
markings on the rotary lock and on the housing
must be aligned with each other.
Onlyembraceonesingleconductorwiththeexible
current sensor, as the currents could otherwise
override each other and cause wrong readings.
Never touch the product above the grip
area (4) / above the display during
measurement. The product is very sensitive
and could display incorrect readings in such
a case.
c) Measuring procedure
The measuring range of the product is of max. 3000 A. When measuring more than 3000 A, the display will
show “OL”.
• Switch on the product by pressing and holding the /Hold button (2) for 2 seconds.
• The product immediately starts measuring the alternating current of the electric conductor embraced by the
exiblecurrentsensor(5);thereadingappearsinthedisplay(1).
• Brieypressthe /Hold button to freeze the displayed value. “HOLD” appears in the left corner of the display.
• Brieypressthe /Hold button again in order for the display (1) to show the current value again; “HOLD” will
disappear.
For better readability, press the light button (3) to switch the background light of the display on or off.
• Switch off the product by pressing the /Hold button for 2 seconds.