Data Sheet

Voltage supply: 380 - 415 V/AC, 50 Hz, three-phase current
Over-voltage category: CAT III (home installation)
Power input: < 20 mA
Plug: CEE - 16A (ST-16B)
CEE - 32A (ST-32B)
Dimensions (L x W x H): 131 x 94 x 54 mm
Weight: 456 g (ST-16B)
540 g (ST-32B)
Diagnosis Display
All displays are green.
The socket is connected correctly. L1, L2, L3, N and PE are present.
The rotating field rotates clockwise.
The phase displays (L1, L2, L3) flash red.
L1, L2, L3, N and PE are present. A phase is interchanged.
The rotating field rotates anti-clockwise.
The phase display L1 is off, L2 and L3 flash red.
Error: Phase L1 is missing or interrupted.
The phase display L2 is off, L1 and L3 flash red.
Error: Phase L2 is missing or interrupted.
The phase display L3 is off, L1 and L2 flash red.
Error: Phase L3 is missing or interrupted
The display N flashes red. The phase displays (L1-L3) may correspond to the diagnoses
above (correct or error).
Error: The neutral wire N is missing or interrupted. A phase is interchanged, if an additional
phase diagnosis (phase display L1-L3) shows an error.
The PE display is off. The phase displays (L1-L3) and display N may correspond to the
diagnoses above.
Error: The earth (PE) is missing or interrupted. No device must be connected to the socket.
Let a specialist check the socket.
TECHNICAL DATA
This data sheet is published by Voltcraft®,
Lindenweg 15, D-92242 Hirschau/ Germany, Phone +49 180 586 582 7. The data sheet reflects the current technical specifications at time of print. We
reserve the right to change the technical or physical specifications.
© Copyright 2022 by Voltcraft
®
.
101017_V2_1221_01_PIX_ds