Technical data
23
Service parameters must only be changed or adjusted by qualified service personnel
Parameter
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
Description
Minimum setting for flow sensor
Unused
Unused
Unused
Unused
Unused
Unused
Unused
Maximum fan speed for heating
(hundreds)
Maximum fan speed (units)
Unused
Unused
Minimum fan speed (hundreds)
Minimum fan speed (units)
Ignition fan speed
Pump over-run
Unused
Set point drop before re-lighting
(heating)
Set point overshoot before burner
off (heating)
Unused
Unused
Unused
Unused
Heating anti-cycle
Unused
Unused
Temperature differential required
for modulation
Unused
Unused
Unused
Unused
Temporary manual fan speed
setting (20 minutes)
Unused
Unused
Unused
Unused
Unused
Normal output/off/minimum output/
off cycle
Range
5 °C - 60° C
10 - 55 (RPM x 100)
00 - 99 (RPM)
05 - 55 (RPM x 100)
00 - 99
05 - 55 (RPM x 100)
01 - 99 minutes
0 °C - 20 °C
0 °C - 10 °C
0 - 30 (1=10.2 secs.)
5 °C - 40 °C
0% - 100%
00 = OFF, 01 = ON
Factory setting
Pinnacle 26
20° C
-15
20
-1
0
25
00
20
55 (5500 RPM)
00
55
00
17 (1700 RPM)
00
44* (4400 RPM)
10 minutes
1
5 °C
2 °C
-3
5
15
-2
9 (91.8 secs.)
0
3
25 °C
-1
15
00
00
-1 (= OFF)
24
00
35
10
20
00
New setting
Factory setting
Pinnacle 16
20 °C
-15
20
-1
0
25
00
20
40* (4000 RPM)
00
40
00
13* (1300 RPM)
00
55* (5500 RPM)
10 minutes
1
5 °C
2 °C
-3
5
15
-2
9 (91.8 secs.)
0
3
25 °C
-1
15
00
00
-1 (= OFF)
24
00
35
10
20
00
operating mode . If the CO
2
reading is incorrect,
the maximum gas pressure must be adjusted as
follows:
● Using a suitable screwdriver, very slowly turn
the maximum adjustment screw (fig. 30) –
clockwise to increase, counter clockwise to
decrease – until the correct value is displayed
on the CO
2
analyser (allow time for the analyser
to stabilise).
● Using the procedure detailed in section 7.4,
change the power momentarily from maximum
to minimum, then back to maximum.
● Check that the correct value is still being
obtained. If not, repeat the above procedure.
● Press the
+
and
-
buttons at the same
time to return to the normal operating mode.
Isolate the appliance from the electrical supply
and remove the analyser test probe from the
analysis test point and refit cap. Refit the air
chamber cover. Refit appliance casing.
NOTE
You should ensure that all radiators or heat
emitters are fully open during the above
procedures. This will ensure that the fan speed
(output) of the boiler is not compromised due to a
high flow temperature.
*This is the setting for Natural Gas. On LPG versions, the factory setting is:
Parameter
13
17
19
Description
Maximum fan speed for heating
(hundreds)
Minimum fan speed (hundreds)
Ignition fan speed
Range
10 - 55 (RPM x 100)
05 - 55 (RPM x 100)
05 - 55 (RPM x 100)
Factory setting
Pinnacle 26
55 (5500 RPM)
17 (1700 RPM)
30* (4400 RPM)
New setting
Factory setting
Pinnacle 16
41* (4100 RPM)
14* (1400 RPM)
39* (3900 RPM)