Technical data

17
Press the
mode
button until “INFO” appears
in the display.
Press the
S
button until the appropriate step
number is shown in the left side of the display.
The measured value of each step is shown on
the right side of the display.
Press the
mode
button until “Stby” appears
in the display to return to the stand-by mode.
5.12 SETTING THE SYSTEM DESIGN PRESSURE
The design pressure should be a minimum of 1
bar and a maximum of 1,5 bar.
The actual reading should ideally be 1 bar plus
the equivalent height in metres (0,1 bar = 1
metre) to the highest point in the system above
the base of the appliance (up to the maximum
of 1,5 bar total).
N.B. The safety valve is set to lift at 3 bar/30
metres/45 psig.
To lower the system pressure to the required
value, pull lever on head of safety valve to release
water until the required figure registers on the
pressure gauge (fig. 1).
5.13 REGULATING THE CENTRAL HEATING
SYSTEM
Fully open all radiator and circuit valves and run
the appliance for both heating and hot water until
heated water is circulating. If conditions are warm
remove any thermostatic heads. Adjust radiator
return valves and any branch circuit return valves
until the individual return temperatures are correct
and are approximately equal.
5.14 CHECKING DYNAMIC GAS PRESSURE
Isolate the appliance from the electrical supply
and remove the appliance casing as described in
section 4.10. Unclip and remove the front air
chamber cover.
Attach a suitable manometer to the inlet test
nipple of the gas valve.
Restore the electrical supply to the boiler and
generate a request for central heating via the
room thermostat and/or timer.
Press the
mode
and
+
buttons at the same
time, the boiler will now run at full power for 15
minutes.
The dynamic gas pressure will now be shown on
the manometer, and should be 20 mbar +/- 1 mbar.
If the dynamic gas pressure is out-with the
tolerance range, you should contact the gas
supplier for advice.
Press the
+
and
-
buttons at the same
time to return to the normal operating mode.
Isolate the appliance from the electrical supply,
remove the manometer from the inlet test nipple,
tighten the test nipple screw, and check for
soundness.
Refit the air chamber cover and appliance casing
in the reverse order.
5.15 FINAL CHECKS
ENSURE ALL TEST NIPPLES ON THE
APPLIANCE GAS VALVE ARE TIGHT AND
HAVE BEEN CHECKED FOR SOUNDNESS.
ENSURE THE APPLIANCE FLUE SYSTEM IS
FITTED CORRECTLY AND IS PROPERLY
SECURED.
ENSURE ALL PIPE WORK IS RE-CHECKED
FOR SOUNDNESS.
RE-FIT APPLIANCE CASING.
COMPLETE APPLIANCE LOGBOOK.
Complete details of the boiler, controls, installation
and commissioning in the logbook supplied with
the boiler. This is an important document, which
must be correctly completed and handed to the
user. Failure to install and commission the
appliance to the manufacturers instructions may
invalidate the warranty.
5.16 INSTRUCTING THE USER
Hand over all documentation supplied with this
appliance – including these instructions – and
explain the importance of keeping them in a safe
place.
Explain to the user how to isolate the appliance
from the gas, water and electricity supplies, and
the locations of all drain points.
Show the user how to operate the appliance and
its associated controls correctly.
Show the user the location of the filling valve and
how to top-up the system pressure correctly and
show the location of all manual air release points.
Explain to the user how to turn off the appliance
for both long and short periods and advise on the
necessary precautions to prevent frost damage.
Step number Information displayed
1
2
3
4
5
6
7
8
9
A
Temperature at flow sensor
Temperature at return sensor
Unused
Unused
Unused
Required temperature (as set at parameter 4)
Temperature rise of flow sensor (measured in °C per
second)
Temperature rise of return sensor (measured in °C
per second)
Unused
Unused