Technical data
6
Key Location Minimum distance
A Below an opening (window, air-brick, etc.) 300 mm
B Above an opening (window, air-brick, etc.) 300 mm
C To the side of an opening (window, air-brick, etc.) 300 mm
D Below gutter, drain-pipe, etc. 25 mm
E Below eaves 25 mm
F Below balcony, car-port roof, etc. 25 mm
G To the side of a soil/drain-pipe, etc. 25 mm (60mm for 80/125 - 5” flue)
H From internal/external corner 25 mm (60mm for 80/125 - 5” flue)
I Above ground, roof, or balcony level 300 mm
J From a surface or boundary facing the terminal 600 mm
K From a terminal facing a terminal 1200 mm
L From an opening in the car-port into the building 1200 mm
M Vertically from a terminal on the same wall 1500 mm
N Horizontally from a terminal on the same wall 300 mm
P From a structure to the side of the vertical terminal 300 mm
Q From the top of the vertical terminal to the roof flashing As determined by the fixed collar
of the vertical terminal
R To the side of a boundary 300 mm
S To the side of an opening or window on a pitched roof 600 mm
T Below an opening or window on a pitched roof 2000 mm
V From a vertical terminal to an adjacent opening (window, air-brick, etc.) (call Vokera technical for advice)
W From a vertical terminal to an adjacent vertical terminal 300 mm (only if both terminals are the same hight)
Fig. 4
radiators tends to increase. By keeping ÄT constant, the
reduction in the flow rate is obtained by changing the
operating curve, which produces a lower return
temperature that in turn favours high boiler performance
and the reduction of electricity consumption.
Operationally:
- Access parameter 90
- Set the parameter at a value between 2 and 40 (normally
between 10 and 20).
3 - VARIABLE SPEED CIRCULATION UNIT WITH
MAXIMUM FIXED MAXIMUM SPEED MODE (P90 = 1)
In this mode the modulating circulation unit works
constantly at maximum speed.
It is used on plants with a high load loss in which the
boiler’s head must be used as much as possible in order
to guarantee sufficient circulation (plant flow rate at
maximum speed lower than 600 litres per hour).
This is used when bottles of mixture are involved, with
high flow rates in the circuit downstream.
Operationally:
- Access parameter 90
- Set the parameter = 1
4 – EXCEPTIONAL USE OF A STANDARD CIRCULATION UNIT
WITHOUT SPEED ADJUSTMENT (P90 = 0)
This mode must be used in exceptional cases in which the boiler
is to be used with a traditional circulation unit without a speed
adjustment. It presupposes that the adjustable speed circulation
unit has been removed and replaced with a non-adjustable speed
circulation unit. Warning !!!! the BE06 board connected to
connector CN9 must be removed and replaced with a connector
with a jumper to be inserted into connector CN9. This latter
connection is obligatory and if not formed may cause the system to
malfunction.
Operationally:
- Access parameter 90
- Set the parameter = 0
HIGH
TEMPERATURE
(radiators)
LOW
TEMPERATURE
(floor)
ΔT constant
(2 P90 40)
EXTERNAL SENSOR YES
(TERMOREGULATION)
PROPORTIONAL
(P90 = 41)
EXTERNAL SENSOR NO
(NO TERMOREGULATION)
PROPORTIONAL
(P90 = 41)
PROPORTIONAL
(P90 = 41)
CONFIGURATIONS RECOMMENDED BY THE MANUFACTURER