Info 3 displays the set heating temperature
Info 4 displays the set domestic hot water temperature.
If you don’t make any selection within 10 seconds, the boiler
automatically exits the function; if you want to exit immediately,
press the
key.
5.9.3 INFORMATION MODE SERVICE
It is possible to display information that can be helpful for the
Service Engineer.
Press for 10 seconds the button : the INF2 will be displayed.
Every pressing corresponds to a different information.
5.9.4 ADJUSTING APPLIANCE PARAMETERS
The appliance is delivered with pre-set parameters. Some param-
eters can be changed or adjusted if required. For further details,
please refer to section 7.
5.10 SETTING THE SYSTEM DESIGN PRESSURE
The design pressure should be a minimum of 0.5 BAR and a
maximum of 1.5 BAR.
The actual reading should ideally be 1 BAR plus the equivalent
height in metres (0.1 BAR = 1 metre) to the highest point in the
system above the base of the appliance (up to the maximum of 1.5
BAR total).
N.B. The safety valve is set to lift at 3 BAR/30 metres/45 psig.
To lower the system pressure to the required value, drain off some
water from the appliance drain valve until the required figure
registers on the pressure gauge (see fig. 1).
Fig. 19
Step Description Unit
01 Temperature at flow sensor °C
02 Temperature at return sensor °C
03 Temperature at hot water outlet sensor °C
04 Unused
05 Unused
06 Unused
07 Flow meter speed lt/min
08 Fan speed/100 rpm
10-17 Historical alarms
18 Time metering cleaning heat exchanger
Lista INF2