Linea ONE High efficiency combi boiler Installation & Servicing Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER Vokèra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK.
Contents Design principles & operating sequence 1.1 1.2 1.3 1.4 1.5 1.6 Principle components Mode of operation Mode of operation (Heating) Mode of operation (DHW) Safety devices Optional accessories Technical data 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.9A 2.9B 2.10 2.11 2.12 2.
INSTALLATION AND SERVICING INSTRUCTIONS INTRODUCTION There are no banned substances used in the manufacture of these appliances. The Linea ONE is a high-efficiency combination boiler with inputs to heating 30 kW & DHW of 38 kW. Each appliance – by design – incorporates electronic ignition, circulating pump, expansion vessel, safety valve, water pressure sensor and automatic by-pass. The Linea ONE is produced as room sealed, category II2H3P appliances, suitable for internal wall mounting applications only.
PRIMARY INFORMATION CONTROLS INTERFACE SECONDARY INFORMATION DISPLAY 1 9 4 2 10 11 3 1 5 12 6 13 °C 4 5 14 7 6 2 8 3 9 7 8 1 2 1 Info button Enables the function that allows the access to some information regarding the boiler operation. 3 2 Memory button Enables the Memory function. 4 5 3 Heating temperature adjustment button Allows the access to the adjustment of the heating water temperature by using the selector.
SECTION 1 - DESIGN PRINCIPLES AND OPERATING SEQUENCE 1.
SECTION 2 - TECHNICAL DATA 2.1 Central Heating Heat input (kW) Maximum heat output @ 60/80 °C (kW) Maximum heat output @ 30/50 °C (kW) Minimum heat output @ 60/80 °C (kW) Minimum heat output @ 30/50 °C (kW) Minimum working pressure Maximum working pressure Minimum flow rate 2.2 Domestic Hot Water Maximum input (kW) Maximum output (kW) Minimum input (kW) Flow rate (35 °C rise) Maximum inlet pressure Minimum inlet pressure Minimum flow rate 2.
2.11 Emissions NOx (max-min) CO (max-min) CO2 (max-min) CO/CO2 ratio (max) CO/CO2 ratio (min) Linea ONE 71 - 44 mg/kWh 215 - 32 mg/kWh 9,5 - 9,5 % 0,002 to 1 0,0003 to 1 Ref. Condition 15 °C, 1013,25 mbar, dry gas NOTE: L.P.G. data refer to section 10 2.
3 - VARIABLE SPEED CIRCULATION UNIT WITH MAXIMUM FIXED MAXIMUM SPEED MODE (P90 = 1) In this mode the modulating circulation unit works constantly at maximum speed. It is used on plants with a high load loss in which the boiler’s head must be used as much as possible in order to guarantee sufficient circulation (plant flow rate at maximum speed lower than 600 litres per hour). This is used when bottles of mixture are involved, with high flow rates in the circuit downstream.
SECTION 3 - GENERAL REQUIREMENTS (UK) This appliance must be installed by a competent person in accordance with the Gas Safety (Installation & Use) Regulations. 3.1 RELATED DOCUMENTS The installation of this boiler must be in accordance with the relevant requirements of the Gas Safety (Installation & Use) Regulations, the local building regulations, the current I.E.E.
3.6.8 FREQUENT FILLING Frequent filling or venting of the system may be indicative of a leak. Care should be taken during the installation of the appliance to ensure all aspects of the system are capable of withstanding pressures up to at least 3 bar. 3.7 ELECTRICAL SUPPLY The appliance is supplied for operation on 230V @ 50Hz electrical supply; it must be protected with a 3-amp fuse. The method of connection to the mains electricity supply must allow for complete isolation from the supply.
SECTION 3A - GENERAL REQUIREMENTS (EIRE) This appliance must be installed by a competent person in accordance with and defined by, the Standard Specification (Domestic Gas Installations) Declaration (I.S. 813). 3A.1 RELATED DOCUMENTS The installation of this boiler must be in accordance with the relevant requirements of the local building regulations, the current ETCI National Rules for Electrical Installations and the bylaws of the local water undertaking.
SECTION 4 - INSTALLATION 4.1 DELIVERY Due to the weight of the appliance it may be necessary for two people to lift and attach the appliance to its mounting. The appliance is contained within a heavy-duty cardboard carton. Lay the carton on the floor with the writing the correct way up. 4.
Vertical flue Part No. 29450122 531 532 29450123 29450124 29450125 29450126 29450127 29450128 529 terminal and accessories Description Vertical flue terminal Pitched roof flashing plate Flat roof flashing plate 90-degree bend 45-degree bends (pair) 500mm extension 1000mm extension 2000mm extension Telescopic extension Wall bracket pack (5) Length 1000mm N/A N/A N/A N/A 500mm 1000mm 2000mm 350/730mm 208mm Using the dimensions given in fig.
• • • • Consideration must also be given to the fact that there is the possibility of a small amount of condensate dripping from the terminal. Ensure that the entire flue system is adequately supported, use at least one bracket for each extension. The entire flue system must be adequately insulated to maintain heat within the flue system thereby reducing the possibility of condensate production.
Fig. 12 4.6 CONNECTING THE GAS AND WATER IMPORTANT - REAR SPACER KIT If you intend to run the pipework vertically behind the appliance, it will be necessary to use the rear spacer kit (part code 435). It will also be necessary to adjust the pitch of the fixing jig to compensate for the increase in the depth of the appliance. The appliance is supplied with a fixing jig that includes service valves (fig. 14). The service valves are of the compression type.
4.6.5 SAFETY VALVE (fig. 14) Connect a discharge pipe to the fixing jig connection and tighten. The discharge pipe must have a continuous fall away from the appliance to outside and allow any water to drain away thereby eliminating the possibility of freezing. The discharge pipe must terminate in a position where any water – possibly boiling – discharges safely without causing damage or injury, but is still visible.
SECTION 5 - COMMISSIONING 5.1 GAS SUPPLY INSTALLATION 5.7 INITIAL LIGHTING Inspect the entire installation including the gas meter, test for tightness and purge. Refer to BS 6891 for specific instruction. Ensure the electrical supply to the appliance is switched on. Press the ON/OFF switch to switch the appliance ON (indicated by active display), ensure any external controls are switched to an ‘ON’ position and are calling for heat.
Info 3 Info 4 displays the set heating temperature displays the set domestic hot water temperature. If you don’t make any selection within 10 seconds, the boiler automatically exits the function; if you want to exit immediately, key. press the 5.9.3 INFORMATION MODE SERVICE It is possible to display information that can be helpful for the Service Engineer. Press for 10 seconds the button : the INF2 will be displayed. Every pressing corresponds to a different information. 5.9.
5.11 REGULATING THE HOT WATER The appliance is fitted with a flow rate restrictor that limits the maximum flow rate that can be drawn through the appliance. The restrictor eliminates the need to manually adjust the DHW flow rate. However if it is felt necessary to further increase or decrease the available flow rate, spare restrictors are included in the accessory pack. The spare flow rate restrictors can be fitted to either increase or decrease the maximum flow rate.
SECTION 6 - SERVICING INSTRUCTIONS 6.1 GENERAL 6.4 COMPONENT REMOVAL PROCEDURE To ensure the continued safe and efficient operation of the appliance, it is recommended that it is checked and serviced at regular intervals. To ensure correct and safe operation of the appliance, it is essential that any worn or failed component be replaced only with a genuine Vokera spare part.
6.6 SAFETY VALVE (fig. 23) 6.11 PRINTED CIRCUIT BOARD (fig. 25) Carry out component removal procedure as described in 6.4. Disconnect the outlet pipe (A) from the safety valve, remove safety valve locking pin (B) from the hydraulic manifold. Replace in the reverse order. Carry out component removal procedure as described in 6.4. Lift the control fascia upward and rotate it.
6.13 ELECTRODE & CONDENSE SENSOR (fig. 27) 6.15 BURNER (fig. 29) Carry out component removal procedure as described in 6.4. Unclip and remove the air chamber front and RH side covers. Disconnect the electrode lead and ancillary wiring from their respective connectors. Remove the 2 retaining screws (A) for electrode (B) and remove. Remove the retaining nut (C) for condense sensor (D) and remove. Carry out component removal procedure as described in 6.4.
move the locking pin (A) that secures the valve housing cover to the hydraulic manifold. Gently prise the valve assembly from the manifold. Replace in the reverse order ensuring that the seating assembly is inserted properly. Ensure all seals are in good condition, taking care to ensure they are replaced correctly. A B A G Fig. 31 6.17 FLOW RESTRICTOR (fig. 32) Carry out the component removal procedure as described in 6.4. Disconnect the cold water inlet pipe at the DHW flow meter (A).
rubber condense pipe (C) from the condense trap. Carefully remove the condense trap. Replace in the reverse order. A 6.26 FLUE COLLECTOR REMOVAL (fig. 37) Carry out component removal procedure as described in 6.4. Unclip and remove the air chamber front and left side covers. Locate and remove the screw (A) that secures the flue gas analysis test point cover (B). Remove the clip and the fumes thermostat. Gently pull down and to the left and ease the flue collector from its location.
SECTION 7 - CHECKS, ADJUSTMENTS AND FAULT FINDING 7.1 CHECKING APPLIANCE OPERATION When carrying out any repairs or servicing to the appliance, the relevant commissioning procedure must be undertaken to ensure the continued safe operation of the appliance. Particular attention should be made to ensure gas tightness, water tightness, and the electrical integrity of the appliance. you select Comfort button, the boiler should be ready to supply the water at the desired temperature. ● 7.
● ● ● Touch & Go Function: if you don’t wish to keep the Memory function always enabled or if you need hot water to be ready fast besides the usual habits memorized, it is possible to perform the domestic hot water pre-heating only a few moments before the request. Due to Touch & Go function, by turning on and off the tap the instantaneous pre-heating function enables, which prepares hot water only for that request.
7.3 SERVICE MODE & PARAMETERS This boiler is equipped with a new generation of electronic boards, which allow a better personalization by setting / adjusting the machine’s operating parameters, in order to answer the installation and/or usage needs. The programmable parameters are indicated in the table at page 24. The parameters programming must be done with the boiler on OFF position. Press the key until you see “ENERGY FOR LIFE” scrolling on display.
PARAMETER N° PARAMETER PAR. UNITÀ This parameter is not used on this model. Do not modify This parameter is not influential 3 10 Building structure DHW-type 11 12 13 14 20 Max set-point for DHW This parameter is not used on this model. Do not modify This parameter is not used on this model. Do not modify This parameter is not used on this model.
7.4 ADJUSTMENTS If adjustments are required again, for example after ordinary maintenance you need to replace the gas valve or after converting from natural gas to LPG or from LPG to natural gas, proceed as follows. Maximum and minimum power, minimum and maximum heating, must be adjusted in the indicated sequence and only by qualified personnel from the Technical Assistance Service. - Turn off the general system power switch - Remove the casing (fig.
7.5 COMBUSTION ANALYSIS TEST A combustion analysis check can easily be carried out on the appliance via the test points located on the top of the appliance, however you must check that the CO2 values are set correctly (see 7.4). - Insert the flue gas analyser probe into the flue gas test point (see fig. 37). - Operate the boiler in HH - LL and compare the values with those shown in 7.4.6. If different adjust the gas valve according to 7.4.6. and 7.4.7. 7.
Code 11 12 13 23 25 27 41 60 71 77 78 Reason false flame restart ignition check the wiring harness check the wiring harness high limit flow temperature probe high limit return temperature probe low water pressure DHW NTC error flow NTC error (2nd CH) over heat underfloor thermostat (2nd CH) flow/return ΔT error (2nd CH) Code 10 14 15 20 21 22 24 26 28 29 34 37 40 42 50-59 70 72 79 80-83 91 Reason no flame detected check the wiring harness false flame high limit thermostat/fume thermostat check the wiring
SECTION 8 - WIRING DIAGRAMS 8.1 EXTERNAL WIRING The appliance comes with a factory fitted link to allow basic operation of the boiler via the mode selector switch. If external controls are to be added to the system, they must be connected to the appliance as shown in the following diagrams. For advice on controls that are not featured in this book, please contact Vokera technical on 0844 391 0999. F= Fuse 3,15AF 8.2 TYPICAL CONTROL APPLICATIONS The appliance can be used with the following controls: Fig.
Key AE02X Main PCB TR1 Main transformer F1-F2 Fuse 4A F J1-J24 Connettors CN1-CN12 Connettors C.S. Condensate sensor F.S. (2) Flame sensor AF0X Display board D.H.W.TDomestic hot water temperature F.M. Flow meter WPS Water pressure switch F Hv Fan power supply 230 V F Lv Fan signal control FS Flue sensor F.O.H.
32 PCB AE01A-P2X AE01X PLUG or CONNECTION CN1 CN2 DESIGNATION Flow, return, condense sensor DHW sensor, DHW flow meter, water pressure sensor Underflow system overheat temperature RS232 PC interface Display board connection Unused Unused Unused AE01X AE01X AE01X AE01X AE01X AE01X CN3 CN4 CN5 CN8 CN9 CN10 PCB AE01X AE01X AE01X AE01X AE01X AE01X AE01X AE01X AE01X PLUG or CONNECTION J1 J2 J3 J4 J5 J6 J7 J8 J9 AE01X AEO1X AE01X AE01X J10 J12 J11-J13-J14 J15 DESIGNATION Earth Unused Incoming 230V suppl
SECTION 9 - EXPLODED DIAGRAMS Table 1 2 31 1 226 25 20 300 18 38 301 302 89 90 226 26 34 303 POS.
Table 2 25 201 24 439 385 63 433 288 201 22 2 434 436 441 265 432 438 6 4 442 433 290 265 351 7 432 439 1 26 521 433 438 37 105 351 328 328 28 30 288 432 47 435 444 443 61 48 288 50 432 265 266 435 351 350 328 353 28 266 62 353 366 27 366 34 35 9 288 10 12 436 11 600 POS.
Table 3 72 73 71 633 287 476 1 477 476 477 633 7 9 201 2 247 704 10 200 200 343 69 17 2 290 200 700 6 26 432 288 288 290 3 432 701 702 27 25 512 595 594 372 703 66 538 POS.
Table 4 27 2 16 27 613 79 19 67 4 486 35 497 46 2 5 200 12 88 13 72 69 3 15 39 700 POS.
Table 5 27 487 12 552 7 637 1 482 700 475 POS. 1 7 12 27 475 482 487 552 637 700 DESCRIPTION Condensing exchanger assembly Conveyor Flue drain connection Nut screw Outlet heat exch.seal gasket Inlet heat exch.
SECTION 10 - LPG INSTRUCTIONS 10.1 RELATED DOCUMENTS BS BS BS BS BS 6798 5449 5446 5440 5482 PART 1 PART 1 PART 1 INSTALLATION OF BOILERS OF RATED INPUT NOT EXCEEDING 60 kW FORCED CIRCULATION HOT WATER SYSTEMS INSTALLATION OF GAS HOT WATER SUPPLIES FOR DOMESTIC PURPOSES FLUES DOMESTIC BUTANE & PROPANE GAS BURNERS IN PERMAMENT DWELLINGS 10.
40
RANGE RATED - EN 483 The max CH input of this boiler has been adjusted to_____ kW, equivalent to _____ rpm max CH fan speed. Cod. 20023652 - 07/10 - Ed. 0 Date___/____/____ Signature _____________________ Boiler serial number _____________________ Registered address: Vokèra Ltd Borderlake House Unit 7 Riverside Industrial Estate London Colney Herts AL2 1HG enquiries@vokera.co.uk www.vokera.co.uk www.vokera.