The threshold is configured under Power Management in the cluster’s Settings dialog box. Each level you
move the vSphere DPM Threshold slider to the right allows the inclusion of one more lower level of priority
in the set of recommendations that are executed automatically or appear as recommendations to be
manually executed. At the Conservative setting, vSphere DPM only generates priority-one
recommendations, the next level to the right only priority-two and higher, and so on, down to the
Aggressive level which generates priority-five recommendations and higher (that is, all recommendations.)
NOTE The DRS threshold and the vSphere DPM threshold are essentially independent. You can
differentiate the aggressiveness of the migration and host-power-state recommendations they respectively
provide.
Host-Level Overrides
When you enable vSphere DPM in a DRS cluster, by default all hosts in the cluster inherit its vSphere DPM
automation level.
You can override this default for an individual host by selecting the Host Options page of the cluster's
Settings dialog box and clicking its Power Management setting. You can change this setting to the following
options:
n
Disabled
n
Manual
n
Automatic
NOTE Do not change a host's Power Management setting if it has been set to Disabled due to failed exit
standby mode testing.
After enabling and running vSphere DPM, you can verify that it is functioning properly by viewing each
host’s Last Time Exited Standby information displayed on the Host Options page in the cluster Settings
dialog box and on the Hosts tab for each cluster. This field shows a timestamp and whether vCenter Server
Succeeded or Failed the last time it attempted to bring the host out of standby mode. If no such attempt has
been made, the field displays Never.
NOTE Times for the Last Time Exited Standby text box are derived from the vCenter Server event log. If
this log is cleared, the times are reset to Never.
Monitoring vSphere DPM
You can use event-based alarms in vCenter Server to monitor vSphere DPM.
The most serious potential error you face when using vSphere DPM is the failure of a host to exit standby
mode when its capacity is needed by the DRS cluster. You can monitor for instances when this error occurs
by using the preconfigured Exit Standby Error alarm in vCenter Server. If vSphere DPM cannot bring a host
out of standby mode (vCenter Server event DrsExitStandbyModeFailedEvent), you can configure this alarm
to send an alert email to the administrator or to send notification using an SNMP trap. By default, this alarm
is cleared after vCenter Server is able to successfully connect to that host.
To monitor vSphere DPM activity, you can also create alarms for the following vCenter Server events.
Table 112. vCenter Server Events
Event Type Event Name
Entering Standby mode (about to power off host)
DrsEnteringStandbyModeEvent
Successfully entered Standby mode (host power off
succeeded)
DrsEnteredStandbyModeEvent
Chapter 11 Using DRS Clusters to Manage Resources
VMware, Inc. 85