Specifications

65
EATON Pulsar Series and Powerware Series Product Catalogue
9395 225-275 kVA, external battery capacity
Battery configuration UPS load with typical load p.f. 0,9
160 200 225 250 275 kVA
1xBAT CSB HRL 500 9 5 - - - min
2xBAT CSB HRL 500 29 20 17 14 12 min
3xBAT CSB HRL 500 49 37 32 28 24 min
*Load power factor 0,9
Runtimes for UPS with internal batteries (4 x 36 pcs 9 Ah) and external battery cabinet(s) with 24 Ah batteries (oneexternalbatterycabinetcanfit2
stringsof24Ahbatteries)
Internal Battery External Battery
Battery Qty Battery Qty 5 10 15 20 25 30 35 40 kVA
9 Ah 12 V 4 x 36 24 Ah 12 V 1 x 36 268 113 77 56 43 34 25 20 min
9 Ah 12 V 4 x 36 24 Ah 12 V 2 x 36 402 175 115 84 69 57 47 38 min
9 Ah 12 V 4 x 36 24 Ah 12 V 3 x 36 555 243 154 121 90 75 63 54 min
9 Ah 12 V 4 x 36 24 Ah 12 V 4 x 36 > 10 h 318 197 147 123 100 77 66 min
External battery (Panasonic LC-X1224AP) with four internal strings back up table for UPS ratings 20-40 kVA, p.f. 0.7 (typical IT server/computer load).
Runtimes for UPS with internal batteries (4x 36pcs 9Ah) and external battery cabinet(s) with 110W batteries
(one external battery cabinet can fit 2 strings of 24 Ah batteries)
Internal Battery External Battery
Battery Qty Battery Qty 5 10 15 20 25 30 35 40 kVA
9 Ah 12 V 4 x 36 110 WPC12 V 1 x 36 318 132 82 62 47 41 32 25 min
9 Ah 12 V 4 x 36 110 WPC12 V 2 x 36 518 225 138 104 81 66 50 42 min
9 Ah 12 V 4 x 36 110 WPC12 V 3 x 36 > 10 h 318 204 147 114 95 77 66 min
9 Ah 12 V 4 x 36 110 WPC12 V 4 x 36 > 10 h 430 266 198 153 124 103 87 min
External battery (CSB HRL 12110W) with four internal strings back up table for UPS ratings 20-40 kVA, p.f. 0.7 (typical IT server/computer load).
The battery backup table is given with end voltage 1.70 VPC and temperature +25ºC.
The batteries are fully charged and measured after minimum (5) full discharge cycles.
Battery configuration UPS load with typical load p.f.0,8
160 200 225 250 275 kVA
1xBAT CSB HRL 500 12 7 5 3 - min
2xBAT CSB HRL 500 34 25 20 17 15 min
3xBAT CSB HRL 500 57 43 37 33 28 min
UPS Runtime Tables
9390 40-160 kVA, external battery capacity
Battery configuration UPS load with typical load p.f.0,8
40 60 80 100 120 160 kVA
1xBAT (HR250) 30 17 10 - - - min
2xBAT (HR250) 73 44 30 22 15 10 min
3xBAT (HR250) 128 72 51 35 30 21 min
4xBAT (HR250) 180 106 75 54 41 30 min
2xBAT (HR305) 39 22 15 - - - min
2xBAT (HR305) 96 57 40 25 22 15 min
3xBAT (HR305) 160 96 64 45 37 26 min
4xBAT (HR305) 220 136 96 72 55 40 min
1xBAT (HRL12280) 40 24 15 10 7 - min
2xBAT (HRL12280) 100 57 33 30 24 15 min
3xBAT (HRL12280) 144 96 69 50 30 28 min
1xBAT (HRL12330) 47 30 20 13 10 6 min
2xBAT (HRL12330) 116 72 50 36 30 20 min
3xBAT (HRL12330) 163 105 84 60 48 35 min
1xBAT (HRL12500) 80 49 35 24 18 12 min
2xBAT (HRL12500) 196 121 81 60 48 34 min
3xBAT (HRL12500) 266 178 121 92 80 57 min
1xBAT (NSB125) 87 53 36 27 20 12 min
2xBAT (NSB125) 200 128 91 69 55 38 min
3xBAT (NSB125) 305 200 145 115 94 64 min