Specifications

EATON Pulsar Series and Powerware Series Product Catalogue
64
UPS Runtime Tables
9155 and 9355 8-15 kVA runtimes
Runtimes for UPS with internal batteries (UPS load with typical 0.7 p.f.)
Battery Qty 3 4 5 6 7 8 9 10 11 12 13 14 15 kVA
7 Ah 12 V 1 x 32 36 26 20 15 12 10 7 6 - - - - - min
9 Ah 12 V 1 x 32 42 32 24 21 16 15 12 10 9 8 7 6 5 min
7 Ah 12 V 2 x 32 86 66 46 38 33 28 23 20 16 15 13 12 10 min
9 Ah 12 V 2 x 32 95 74 61 44 38 33 29 25 22 20 18 16 15 min
Runtimes for UPS with external battery cabinet
Battery Qty 3 4 5 6 7 8 9 10 11 12 13 14 15 kVA
7 Ah 12 V 3 x 32 130 100 81 68 57 44 39 35 27 24 22 20 18 min
7 Ah 12 V 4 x 32 200 133 108 91 78 69 61 47 40 35 32 29 27 min
7 Ah 12 V 5 x 32 250 182 141 114 95 81 70 61 53 47 43 39 36 min
7 Ah 12 V 6 x 32 316 230 178 144 120 102 89 78 67 60 54 50 45 min
7 Ah 12 V 7 x 32 385 280 217 176 146 124 106 93 82 73 66 60 55 min
7 Ah 12 V 8 x 32 458 333 258 209 174 147 126 110 97 87 79 72 66 min
BladeUPS
Load #42U Racks 4 kW 8 kW 12 kW 24 kW 36 kW 48 kW 60 kW
1 x BladeUPS (12 kW Internal battery) 6 6 1 23 8,7 4,7
+ 1 External Battery Module
9 9 1 41 17,6 9,5
+ 2 External Battery Module
12 12 1 65 28 17
+ 3 External Battery Module
15 15 1 93 43 27
+ 4 External Battery Module
18 18 1 119 55 34
2 x BladeUPS (12 kW N+1 Internal battery) 12 18 1 44 23 13,6
+ 1 External Battery Module
18 24 1 85 41 27
+ 2 External Battery Module
24 30 1 137 65 41
+ 3 External Battery Module
30 36 1 198 93 59
+ 4 External Battery Module
36 42 2 257 119 76
3 x BladeUPS (24 kW N+1 Internal battery) 18 24 1 34 23 8,7
+ 1 External Battery Module
27 33 1 34 41 17,6
+ 2 External Battery Module
36 42 2 102 65 28
+ 3 External Battery Module
45 51 2 147 93 43
+ 4 External Battery Module
54 60 2 190 119 55
4 x BladeUPS (36 kW N+1 Internal battery) 24 30 1 30 13,6 7,3
+ 1 External Battery Module
36 42 2 56 27 14,7
+ 2 External Battery Module
48 54 2 89 41 24
+ 3 External Battery Module
60 66 2 128 59 37
+ 4 External Battery Module
72 78 2 165 76 47
5 x BladeUPS (48 kW N+1 Internal battery) 30 36 1 19 10 6,6
+ 1 External Battery Module
45 51 2 34 21 13,3
+ 2 External Battery Module
60 66 2 54 31 23
+ 3 External Battery Module
75 81 2 77 48 35
+ 4 External Battery Module
90 96 3 98 61 44
6 x BladeUPS (60 kW N+1 Internal battery) 36 42 2 23 13,5 8,7 6,2
+ 1 External Battery Module
54 60 2 41 27 17,6 12,6
+ 2 External Battery Module
72 78 2 65 41 28 21,6
+ 3 External Battery Module
90 96 3 93 59 43 33
+ 4 External Battery Module
108 114 3 119 76 55 42
* Note: each UPS requires the same number of external batteries Time in minutes