Specifications
49
EATON Pulsar Series and Powerware Series Product Catalogue
Eaton 9395 UPS 225 - 1100 kVA
TECHNICAL SPECIFICATIONS
UPS output power rating (0,9 p.f.)
kVA 225 275 450 550 675 825 1100
kW 202 247 405 495 606 742 990
General
Efficiency in double
conversion mode (full load)
>94,5%
Efficiency in double
conversion mode (half load)
94%
Efficiency in Energy Saver
System (ESS)
up to 99%
Distributed parallelling with
Hot Sync technology
5
Internal N+1 redundance
capable
from 225 to 825 kVA
Field upgradeable yes
Inverter/rectifier topology transformer-free IGBT with PWM
Audible noise <76 dB; <80 dB (825 and 1100 kVA)
Altitude (max) 1000 m without derating (max 2000 m)
Input
Input wiring 3 ph + N + PE
Nominal voltage rating (con-
figurable)
220/380, 230/400, 240/415 V 50/60 Hz
Input voltage range +10% / -15%
Input frequency range 45-65 Hz
Input power factor 0,99
Input ITHD less than 4,5%
Soft start capability Yes
Internal backfeed protection Yes
Output
Output wiring 3 ph + N + PE
Nominal voltage rating (con-
figurable)
220/380, 230/400, 240/415 V 50/60 Hz
Output UTHD
<3% (100% linear load); <5% (standard non
linear load)
Output power factor 0,9 (e.g. 247 kW at 275 kVA)
Permitted load power factor 0,7 lagging - 0,8 leading
Overload on inverter
10 min 100-110%; 30 sec 110-125%;
10 sec 125-150%; 300 ms >150%
Overload when bypass
available
Continuous <115%, 20 ms 1000% Note! Bypass
fuses may limit the overload capability
Battery
Type VRLA, AGM, Gel, Wet Cell
Charging method ABM technology or Float
Temperature compensation Optional
Battery nominal voltage
(lead-acid)
480 V (40 x 12 V, 240 cells)
Charging current / Model
Default A
Max* A
275
38
83
550
76
166
825
114
249
1100
152
332
*Limited by maximum UPS input current rating
Dimensions and weights
225 kVA, 275 kVA 1350 x 880 x 1880 mm (wxdxh) 830 kg
225 kVA redundant,
275 kVA redundant
1890 x 880 x 1880 mm 1430 kg
450, 500, 550 kVA 1890 x 880 x 1880 mm 1430 kg
450, 550 kVA redundant 2520 x 880 x 1880 mm 2030 kg
Field upgrade module,
225 or 275 kVA
740 x 880 x 1880 mm 600 kg
675, 825 kVA 3710 x 880 x 1880 mm 2520 kg
675, 825 kVA
+ 1 redundant
4450 x 880 x 1880 mm 3120 kg
1100 kVA 4450 x 880 x 1880 mm 3120 kg
Accessories
External battery cabinets with long-life batteries,
X-Slot connectivity (Web/SNMP, ModBus/Jbus,
Relay, Hot Sync, ViewUPS-X remote display),
integrated manual bypass for 225-550 kVA
Communications
X-Slot 4 communication bays
Serial ports 1 available
Relay inputs/outputs 5/1 programmable
Compliance with standards
Safety (CB certified) IEC 62040-1, IEC 60950-1
EMC IEC 62040-2
Performance IEC 62040-3