Specifications

EATON Pulsar Series and Powerware Series Product Catalogue
48
Eaton 9395 UPS
225 - 1100 kVA
Powerwareseries
Advanced power protection for:
• Bigdatacentersandserverfarms
• Financialservices
• Buildingmanagement
• Telecommunications
• Hospitals
Double conversion UPS
Premium power performance
• Doubleconversionprovidesthehighestlevelofprotection
available by isolating the output power from all input anomalies.
• Withatransformer-freedesignandsophisticatedsensing
and control circuitry the 9395 UPS delivers an efficiency of
upto94,5%.
• Activepowerfactorcorrection(PFC)provides0,99input
powerfactorandlessthan4,5%ITHD,thuseliminatinginter-
ference with other critical equipment in the same network
and enhancing compatibility with generators.
• TheUPSisoptimizedforprotectingmodern0,9p.f.ratedIT
equipment without the need to oversize.
True reliability
• HotSynctechnologymakespossibletoparalleluptofour
UPSs to increase availability or add capacity. The technology
enables load sharing without any communication line, thus
eliminating single point of failure.
• Themulti-module9395canbeconfiguredwithinherent
redundancy–anytimetheloadisbelow50%,thesystem
becomes automatically redundant.
• ABMtechnologychargesbatteriesonlywhennecessary,
preventing batteries corrosion and prolonging batteries serv-
icelifebyupto50%.
Extensive configurability
• The9395isacompletelyintegratedsystemthanincorpo-
rates multiple power modules and system switchgear on
factory pre-wired bases.
• AmultilingualgraphicalLCDdisplaymakespossibletomoni-
tor the UPS status easily.
• Widesoftwareandconnectivityoptionsprovidemonitoring,
management and shutdown capabilities over network
Cost savings and sustainability
• Highlevelofsystemefficiencyenablestoreduceutility
cost, extend battery run times and ensure cooler operating
conditions.
• ComparedtotraditionalUPSdesign,atransformer-freeUPS
isonly50%theweightandoccupiesjust60%thefootprint,
thus reducing impact on shipping.
• Thenewdesignrequires50-80%lessenergyinmanufac-
turing due to less energy required for testing and to the
smaller configuration.
• Pre-wiredconfigurationenablestoreducecablingbusbar
costs and installation time. Front accessible design minimiz-
es installation costs and saves valuable data centre space.
• WithEasyCapacityTestfeaturethe9395cantestitsentire
power train under full load stress without the requirement of
an external load.
• AsingletechnicalplatformusedinEaton´sthree-phaseUPS
products guarantee easy upgrades and similarity in service,
thus lowering total cost of ownership.
• Morethan90%ofthematerialscanberecycled,further
decreasing end-of-life impact.
Due to outstanding green performance, the 9395 has
earned the “An Eaton Green Solution”™ label