Specifications

27
EATON Pulsar Series and Powerware Series Product Catalogue
Eaton EX RT UPS
TECHNICAL SPECIFICATIONS
5 kVA 7 kVA 11 kVA
Active power kVA / kW 5 kVA / 4 kW
(single phase input not available
for 5 kVA)
7 kVA / 4.9 kW 11 kVA / 8 kW
Technology On-line double conversion with PFC (Power Factor Correction) system (applicable to single phase models))
Rated input voltage 200/208/220/230/240/250 V single phase 380/400/415V three phase
Input voltage range (- 30%; + 20%) 230 V; (- 20%, + 15%) 400 V
Input, output frequency range 40-70 Hz, 50 / 60 HZ autoselection, frequency converter as a standard
Output voltage / THDU 200/208/230/240 /250 V +/- 2%; THDU < 2%
Overall efficiency Normal mode 91%, eco mode 97%
THDI THDI < 5% (single phase input value)
Crest factor / short circuit current 3:1 / 100 A 3:1 / 100 A 3:1 / 150 A
Overload capacity >150% 500 ms; 150% 30 s; 125% 60 s; 110% 120 s
Temperature operating 45°C for 8 Hrs (at nominal output power for 230 V or 400V input and 230V output), 40°C continuous
Back-up times* at 70% load
From 10 up to 15 minutes Standard: 1 power mod. 3U + 1 battery mod. EXB 3U = 6U
From 15 up to 20 minutes Standard + 1 battery mod. EXB 3U = 9U
From 40 up to 65 minutes Standard + 2 battery mod. EXB 3U = 12U
Connection
Input /output Terminal block for 13 mm
2
(stranded cable) or 10 mm
2
(solid cable)
Communication
Port type 6 voltage free contacts DB9 2 A 48 V DC, 1 RS 232, RJ11 for remote emergency power off
Slot 1 slot for communication card
Standards and certification
Performance and safety IEC 62040-1/IEC 60950/UL 1778 and CSA 22.2 (applicable to single phase models)
EMC IEC 62040-2; EN 50091-2; FCC class A (applicable to single phase models), EMC B level (option for single phase model)
Certification UL (applicable to single phase models)/TÜV, GS mark,CB, C-Tick,CE, IEC 68-2-6 (vibration tests Marine approval)
Dimensions H x W x D / Weight (single phase input / three phase input)
Eaton EX RT standard backup tower 444.5 x 261.2 x 700 mm
89.5 kg
444.5 x 261.2 x 700 mm
88.3 kg / 89.5 kg
444.5 x 261.2 x 700 mm
94.2 kg / 95.3 kg
Eaton EX RT standard backup Network
Pack rack mounting
261.2 (6U) x 444.5 x 700 mm
97.3 kg
261.2 (6U) x 444.5 x 700 mm
96.1 kg / 97.3 kg
261.2 (6U) x 444.5 x 700 mm
102 kg / 103.1 kg
Eaton EX RT Power module
444.5x130.6x700/130.6 (3U)x444.5x700 mm
24.2 kg
444.5x130.6x700/130.6 (3U)x444.5x700 mm
23 kg / 24.2 kg
444.5x130.6x700/130.6 (3U)x444.5x700 mm
24.9 kg / 26 kg
Battery module Eaton EXB RT
444.5x130.6x650/130.6 (3U)x444.5x650 mm
64.5 kg
444.5x130.6x650/130.6 (3U)x444.5x650 mm
64.5 kg
444.5x130.6x650/130.6 (3U)x444.5x650 mm
68.5 kg
EX RT CLA module / EX RT Transformer
130.6 (3U) x 444.5 x 650 mm / 12 kg /
87 kg
130.6 (3U) x 444.5 x 650 mm / 12 kg /
87 kg
130.6 (3U) x 444.5 x 650 mm / 12 kg /
87 kg
Customer Service & Support
1 year warranty, including battery Free standard replacement for faulty units, including the batteries
Warranty+ Optional 3-years warranty (depending on the country please visit www.eaton.com/powerquality)
* (typical values after 3 discharge cycles, batteries 3-5 years, longer backup times available using the CLA or EXB module, ask for details)
Part Numbers
EX RT 5 EX RT 7 EX RT 11
Input voltage
Single-phase Three-phase Single-phase Three-phase Single-phase Three-phase
Eaton EX RT standard back-up time Tower / 68 054 68 070 68 074 68 110 68 114
Network Pack Rack Format (1) / 68 056 68 072 68 076 68 112 68 116
EXB RT battery module / EXB RT battery module with
EPO built-in
/ 68 078 / 68 079 68 078 / 68 079 68 078 / 68 079 68 118 / 68 119 68 118 / 68 119
Eaton EX RT Power module (for use with EXB or
CLA module)
/ 68 057 68 075 68 077 68 115 68 117
Rack kit for Eaton EX RT Power module / Eaton EXB RT
and CLA
/ 68 001 / 68 002 68 001 / 68 002 68 001 / 68 002 68 001 / 68 002 68 001 / 68 002
Eaton EX RT Transformer module / 68 003 68 003 68 003 68 003 68 003
Eaton EX RT CLA module (2 to 8 hours) / 68 004 68 004 68 004 68 004 68 004
EX RT Battery Integration System (2) / 68 005 68 005 68 005 68 005 68 005
EMC B level filter module / / 68 008 / 68 008 /
EX RT PDU 19” rack format (3) / 66 857 66 857 66 857 66 857 66 857
1.8 m battery connection cable (4) / 68 006 68 006 68 006 68 006 68 006
UPS Control, remote UPS monitor display / 66 080 66 080 66 080 66 080 66 080
1: the Network Pack version includes standard back-up time unit + Network Management Card + rack mounting kit. 2: trolley capacity 8 modules max, casters, adjustable feet. 3: 12 sockets 4 X
IEC 16 A + 8 X IEC 10 A. 4: for non standard inter-module spacing.
Slot for Eaton minislot communication card
9-pin D output connector
RJ11 port for remote emergency power off
Connectors for automatic detection of battery
module(s)
RS 232 communication port
Connector for EXB modules
Manual bypass for hot maintenance
Output connectors
Source switch 1
Source 1 connector
Source 2 connector
Battery circuit breaker