Specifications
23
EATON Pulsar Series and Powerware Series Product Catalogue
TECHNICAL SPECIFICATIONS
700 1000 - 1000 RT2U 1500 - 1500 RT2U 2200 3000 - 3000 XL
Rating (VA/W) 700 VA / 630 W 1000 VA / 900 W (1) 1500 VA / 1350 W (1) 2200 VA / 1980 W 3000 VA / 2700 W (1)
Format Mini tower Mini tower or RT2U (tower/rack 2U) RT2U (tower/rack 2U) and RT3U (tower/rack 3U)
Electrical characteristics
Architecture On-line double conversion with automatic by-pass and power factor correction
Input voltage and frequency ranges
without using batteries
100/120/140/160 V(2) to 284V - 40 to 70 Hz 100/120/160/184 V(2) to 284V - 40 to 70 Hz
Output voltage and frequency 230 V (adjustable to 200/208/220/240/250 V), 50/60 Hz auto-select or
frequency converter mode (3)
230 V (adjustable to 200/208/220/240 V),
50/60 Hz auto-select or frequency converter mode
Connections
Input 1 IEC C14 (10A) socket 1 IEC C20 (16A) or terminal block on HotSwap
MBP HW (Hard-Wired)
Outputs 6 IEC C13 (10A) sockets 8 IEC C13 (10A) sockets + 1 IEC C19 (16A) socket
Remotely controlled Powershare sockets 2 independent groups: 2 + 1 IEC C13 (10A) sockets 2 groups of 2 x IEC C13 (10A) on Eaton EX
Additional outputs with
HotSwap MBP FR/DIN/BS/IEC/HW
4 FR/Schuko sockets or 3 BS sockets or 6 IEC 10A sockets or terminal blocks (HW version)
Additional outputs with
FlexPDU FR/DIN/BS/IEC
8 FR/Schuko sockets or 6 BS sockets or 12 IEC 10A sockets
Battery
Typical backup times for 50 and 70% load (6) except for Eaton EX 3000 XL (5)
EX 16 min / 10 min 18 min / 12 min 13 min / 9 min 17 min / 12 min 15 min / 10 min
EX + 1 EXB / 75 min / 50 min 50 min / 35 min 85 min / 60 min 60 min / 40 min
EX + 4 EXB / 250 min / 200 min 180 min / 120 min 285 min / 200 min 190 min / 150 min
Battery management Automatic weekly test (period adjustable using LCD display or in software supplied), automatic recognition
of external battery units => continuous maximisation of backup time + deep discharge protection
Interfaces
Indicators and display 3 LEDS + adjustable multilingual display: display of measurements, access to control and set-up menus
Communication ports 1 USB port + 1 RS232 serial port and relay contacts (4) + 1 mini terminal block for remote ON/OFF and emergency stop
Communications card slots 1 slot for NMC Minislot card (included in Netpack version) or NMC ModBus/JBus or MC Contacts/Serial
Operating conditions, standards and approvals
Operating temperature noise level 0°C to 40°C continuous, 45 dBA
Performance - Safety - EMC IEC/EN 62 040-3 (VFI-SS-113), IEC/EN 62 040-1-1, IEC/EN 60 950-1 (RD), IEC/EN 62 040-2 C1 Class
Approvals CE, TüV GS, CB report, cTüV-US CE, TüV, CB Report, UL CE, TüV, CB Report, UL
Dimensions (H x W x D) / Weight
EX 242 x 153 x 440 mm /
12.5 kg
242 x 153 x 440 mm /
15 kg
242 x 153 x 490 mm /
18 kg
440 x 131 x 490 mm (7) /
30 kg (3000 XL = 18 kg)
EX RT2U /
86.5 x 438 x 483 mm /
18 kg
86.5 x 438 x 483 mm /
20.5 kg
86 x 440 x 640 mm / 31 kg
EX EXB / 242 x 153 x 440 mm / 21 kg 440 x 131 x 490 mm (7)
EX EXB RT2U / 86.5 x 438 x 483 mm / 24.5 kg / /
Customer Service & Support
2 years warranty Standard product exchange, including the battery
Warranty+ Optional 3-years warranty (depending on the country please visit www.eaton.com/powerquality)
1: Maximum rating with EXB battery units: Eaton EX 1000 = 800 W, Eaton EX 1500 =1200 W and Eaton EX 3000=2400W. 2: Lower limits for <20%, <33%, <66%, >=66% of nominal power (VA). For active
output power greater than 0.7 and 0.8 nominal rating, the lower limit is 180V and 190V respectively. 3: Derated by 15% when used as a frequency converter. 4: USB and RS232 serial ports cannot be
used simultaneously. 5: Except Eaton EX 3000 XL: UPS with high speed charger, without built-in batteries, for custom configurations: ask us for details. 6: Runtimes are shown at 0.7 power factor.
Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc. 7: compatible with 600 mm deep rack
LCD Multilingual display
- 6 languages,
- displays measurements,
- displays alarms,
- access to control and set-up menus.
Panel for batteries replacement (Hot
swappable)
1 USB port + 1 serial port + remote ON/OFF and
emergency stop inputs.
EXB battery unit connector.
EXB units recognised automatically.
8 IEC 10A sockets, including 4 Powershare pro-
grammable sockets and 1 IEC 16A socket.
Communication card slot.
Mountings for HotSwap MBP and FlexPDU.
Eaton EX RT
Eaton EX UPS
Part Numbers 700 1000 1500 2200 3000
EX 68 180 68 181 68 183 68 400 68 402 - XL: 68 404
EX RT2U (includes rack kit) / 68 182 68 184 68 401 68 403
EX RT3U HotSwap. (includes rack kit +
HotSwap MBP)
/ / / FR: 68406 DIN: 68407 BS:
68408
IEC: 68409 HW: 68410
FR: 68412 DIN: 68413 BS:
68414
IEC: 68415 HW: 68416
EX RT2U Netpack
(includes rack kit and NMC card)
/ / 68 411 68 417
EX EXB / 68 185 68 185 68 405 68 405
EX EXB (includes rack kit) RT2U / 68 186 68 186 / /