Specifications
21
EATON Pulsar Series and Powerware Series Product Catalogue
Full user interface:
- ON/OFF button for UPS and outlets
- Load protected/ not protected LED
- Utilised power level/Battery charge level
- Status of switchable outlets
Panel for batteries replacement (Hot swappa-
ble)
1 USB port + 1 serial port + remote ON/OFF
EXB battery unit connector
EXB units recognised automatically
8 IEC 10A sockets, including 4 pro-
grammable sockets
Communication card slot
TECHNICAL SPECIFICATIONS
1250 1750 2500 3000
Rating (VA/W) 1250 VA / 1150 W 1750 VA / 1600 W 2500 VA / 2250 W 3000 VA / 2700 W
Format RT2U (tower / rack 2U) RT2U (tower / rack 2U) RT2U (tower / rack 2U) RT2U & RT3U
Electrical characteristics
Technology Line-Interactive High Frequency (Booster + Fader)
Input voltage and frequency ranges without
using batteries
160V-294V (adjustable to 150V-294V) 47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system),
up to 40 Hz in low-sensitivity mode (programmable using Personal Solution-Pac software.
Output voltage and frequency 230 V (+6/-10 %) (Adjustable to 200 V (10 % derating of output power) / 208 V / 220 V / 230 V / 240 V), 50/60 Hz +/- 0.1 %
Connections
Input 1 IEC C14 (10 A) socket 1 IEC C14 (10 A) socket 1 IEC C20 (16 A) socket 1 IEC C20 (16 A) socket
Outputs 8 IEC C13 (10 A) 8 IEC C13 (10 A) 8 IEC C13 (10 A) sockets
1 IEC C19 (16 A) socket
8 IEC C13 (10 A) sockets
1 IEC C19 (16 A) socket
Remotely controlled sockets 2 groups of 2 x IEC C13 (10 A)
Additional outputs with HS MBP 4 FR/Schuko sockets or 3 BS sockets or 6 IEC 10 A sockets or terminal blocks (HW version)
Additional outputs with FlexPDU 8 FR/Schuko sockets or 6 BS sockets or 12 IEC 10 A sockets
Batteries
Typical backup times for 50 and 70% load*
Evolution S 20/14 mn 14/9 mn 17/11 mn 15/10 mn
Evolution S + 1 EXB 105/60 mn 60/36 mn 85/55 mn 60/42 mn
Evolution S + 4 EXB 300/200 mn 180/115 mn 290/200 mn 210/135 mn
Battery management Automatic weekly test (period adjustable), automatic recognition of external battery units => continuous maximisation of
backup time + deep discharge protection
Interfaces
Communication ports 1 USB port + 1 RS232 serial port and relay contacts (USB and RS232 ports cannot be used simultaneously)
+ 1 mini terminal block for remote ON/OFF and Remote Power Off
Communications card slots 1 slot for NMC Minislot card (included in Netpack versions) or NMC ModBus/JBus or MC Contacts/Serial
Operating conditions, standards and approvals
Operating temperature 0 to 40°C
Noise Level < 45 dBA < 45 dBA < 50 dBA < 50 dBA
Performance - Safety - EMC IEC/EN 62040-1-1 (Safety), IEC/EN 62040-2 EN 50091-2 class B (EMC), IEC/EN 62040-3 (Performance),
IEC/EN 61000-4-2, 61000-4-3, 61000-4-4; 61000-4-5, 61000-4-6, 61000-4-8 (EMI)
Approvals CE, CB report, TÜV
Dimensions W x D x H / Weight
Dimensions 440 x 509 x 86.2 (2U) mm 440 x 509 x 86.2 (2U) mm 440 x 634 x 86.2 (RT2U) mm
440 x 484 x 130.7 (RT3U) mm
440 x 634 x 86.2 (RT2U) mm
440 x 484 x 130.7 (RT3U) mm
Weight of the Tower/Rack 24.3 kg 26.6 kg 33.8 kg 33.8 kg (RT2U) - 34.3 kg (RT3U)
Dimensions of EXB See UPS
Weight of the EXB 30.4 kg 30.4 kg 41.7 kg 41.7 kg
Customer Service & Support
2 years warranty Standard product exchange, including the battery
Warranty+ Optional 3-years warranty (depending on the country please visit www.eaton.com/powerquality)
* Runtimes are shown at 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
Part Numbers S 1250 RT2U S 1750 RT2U S 2500 RT2U
Netpack*
S 3000 RT3U S 3000 RT2U
Netpack*
Convertible Tower/Rack 68 456 68 459 68 463 68 464 68 465
EXB Models 68 470 68 470
2U = 68 472 - 3U =
68 471
2U = 68 472 - 3U =
68 471
2U = 68 472 - 3U =
68 471
* NMC card included in Netpack versions.
Eaton Evolution S 3000 RT2U Netpack