Installation Instructions
Table Of Contents
Specications
Standards IEEE 802.11 b/gO
Frequency range 2.4~2.4835 Ghz
Antenna PCB-mounted chip antenna
Security WPA2
Operating temperature
-25 rC to +50 rC (-13 rF to
+122
rF)
Operating humidity 5–95% RH, non-condensing
Operating mode
Access point / Client
Ingress protection IP20 (IP55 with gasket)
Electrical rating 5 V, 250 mA
Internal memory size 14 MB
Dimensions (LxWxD) [mm (in)] 131.2 x 66.6 x 23 (5.1 x 2.6 x 0.9)
Weight [g (oz)] 85.3 (2.88)
Firmware update MCT 10 Set-up Software version
4.10 or higher
Installation Instructions
VLT
p
Wireless Communication Panel LCP 103
VLT
p
FC Series FC 102, FC 103, FC 202,
FC 301/FC 302, and LD 302
MI38V402 Danfoss A/S © 06/2018 All rights reserved. 3
NOTICE
If the password is not changed, it leaves only 10 minutes for
connecting and performing Drive operations. After this, the
wireless connection closes.
Reset password
If the wireless SSID and password are forgotten, access
parameter group 30-9* Wi LCP via MCT 10 Set-up Software or
LCP 102.
LED Pattern
LED Pattern Description
On Solid
green
The drive is powered on (normal operation).
Wi-Fi
Flashing
white
Connection pairing successful.
Solid
white
The smart device is connected and communi-
cation is OK.
Alarm Flashing
red
An alarm has occurred.
Warn Solid
yellow
A warning has occurred.
MS,
NS1,
NS2
1)
Flashing
orange
Identication of the drive when initiated through
a winking command.
Flashing
orange
Incompatible drive (LED ashes 3 times and then
remains on).
Table 1.1 Descriptions, LED Indicators
1) MS=module status, NS1=network status 1, NS2=Network status 2.
Safe Control
The safe control parameter allows the drive to decide the
motor behavior if the smart device, for example a tablet,
communication is lost. If the limits are set to [1] Stop motor,
the motor stops. If the limits are set to [0] Do nothing, the
motor continues to run. This is only applicable when the
motor is in Run state and if the motor has been started from
the app.
The communication happens between the MyDrive
p
Connect
App and the VLT
p
Wireless Communication Panel LCP 103.
Parameter Limits/options
Parameter 30-97 Wi Timeout Action [0] Do nothing
[1] Stop motor