Specifications

RailCorp Infrastructure Engineering Manual – Signalling
Maintenance Manual
Electric Point Machine Westinghouse Style M70 MKIII TMG E1583
4.1 Motor
4.1.1 Description
The point machine is fitted with a plug-connected series-wound motor, as shown in
Figure 4.1.1. The split field enables a regenerative braking circuit to provide snubbing
at the end of the stroke. The plug connector is indexed to prevent use of a wrong type
motor. If required, the machine can also be fitted with a 110V DC, AC immune
permanent magnet motor.
4.1.2 Removal and Replacement
1. Unplug the lead from the terminal board.
2. Remove the two bolts from the baseplate.
3. Slide the motor towards the end of the machine until the spur gear disengages
from the gear cluster and then remove the motor.
4. Replacement involves the above procedures in reverse order. Care should be
taken to ensure that the spur gear meshes properly and that the location spigot
seats properly before bolting down.
4.1.3 Overhaul
The operation of the motor should be observed during normal monthly maintenance
visits. If it shows signs of abnormal noise, slackness in the bearings or heavy burning
of the commutator, the motor should be exchanged.
Version 1.0 © RailCorp 2009 Page 19 of 52
Issue Date: 1 December 2009 Uncontrolled when Printed