Owner`s manual
Outside fresh air is mandatory when installing this
unit in airtight homes and mobile homes.
When connecting to an outside fresh air source, do not use
plastic or combustible pipe. A 1” minimum (42 mm) ID
(inside diameter) steel, aluminum or copper pipe should be
used. It is recommended, when you are installing a fresh
air system, to keep the number of bends in the pipe to a
minimum.
Installation
OUTSIDE FRESH-AIR CONNECTION:
Figure 16: Outside Air Connection.
EXHAUST AND FRESH AIR INTAKE LOCATIONS:
Freestanding Fireplace Insert
Base of unit to center of flue 20 ” (515 mm) 9” (228 mm)
Side of unit to center of flue 5
3
/16” (132 mm) 5
3
/16” (132 mm)
Center of unit to center of flue 5 ” (146 mm) 5 ” (146 mm)
Base of unit to center of intake 14 ” (372 mm) 3 ” (74 mm)
Side of unit to center of intake 12” (304 mm) 12” (304 mm)
Center of unit to center of intake 1” (25 mm) 1” (25 mm)
20
1
/4"
(515 mm)
14
5
/8"
(372 mm
)
5
3
/16"
(132 mm
)
12"
(304 mm)
5
3
/4"
(146 mm
)
1"
(25 mm)
9"
(228 mm)
3
3
/8"
(86 mm
)
5
3
/16"
(132 mm
)
12"
(304 mm)
5
3
/4"
(146 mm
)
1"
(25 mm)
Figure 17: VF100 Freestanding Inlet and Outlet
Location.
Figure 18: VF100 Fireplace Insert Inlet and Outlet
Location.
INSTALL VENT AT CLEARANCES SPECIFIED BY
THE VENTING MANUFACTURER
16