Installation
CLEARANCES TO COMBUSTIBLES - FREESTANDING:
30"
(76cm)
48"
(122cm)
36"
(91cm)
6"
(152 mm)
1"
(25mm)
1"
(25mm)
6"
(152mm)
Back Wall
Side Wall
Adjacent Wall
Floor
Protection
Figure 13: VF100 FS Clearance to Combustibles.
Minimum Alcove width - 36 inches (91 cm)
Minimum Alcove height - 48 inches (122 cm)
Maximum Alcove depth - 30 inches (76 cm)
Figure 14: VF100 FS Alcove Size.
When installing this unit on a combustible floor (for
example linoleum, hardwood flooring) a non-combustible
hearth pad must be under the unit. The pad must extend
at least the width of the appliance [22” (558 mm)] and at
least the depth of the appliance plus 6” (153 mm) in front
of the appliance [30” (775 mm)].
Side wall to unit - 6 inches (15 cm)
Back wall to unit - 1 inches (2.5 cm)
Corner to unit - 1 inches (2.5 cm)
Door front to edge of floor protection
- 6 inches (15 cm)
NOTE: These dimensions are minimum clearances but
it is recommended that you ensure sufficient room for
servicing, routine cleaning and maintenance.
CLEARANCES TO ALCOVE - FREESTANDING:
1
0
" (
2
5
4
mm
) M
a
ntl
e
Min. 8"
(203mm)
Min. 8"
(203mm)
6" (152mm)
Figure 15: VF100 FPI Clearance to Combustibles.
Refer to Figure 15.
Side wall to unit - 8 inches (20.3 cm)
Mantel projection - 10 inches (25.4 cm)
Mantel to top of unit - 8 inches (20.3 cm)
Top facing to unit - 8 inches (20.3 cm)
Side facing to unit - 6 inches (15.2 cm)
Floor protection - 6 inches (15.2 cm)
on either side and to the front must be protected by
non-combustible material.
CLEARANCES TO COMBUSTIBLES - INSERT: