Installation
hoRizontaL exhauSt thRough WaLL inStaLLation - fReeStanDing
Vent installation: install vent at clearances specified by the vent manufacturer.
A chimney connector shall not pass through an attic or roof space, closet or similar concealed spaces,
or a floor, or ceiling� Where passage through a wall or partition of combustible construction is desired,
the installation shall conform to CAN/CSA-B365 Installation Code for Solid-Fuel-Burning Appliances and
Equipment� Only use venting of L or PL type with an inside diameter of 3 or 4 inches (7�6 or 10�1 cm)�
1� Choose a location for your stove that meets the requirements stated in this manual and allows
installation with the least amount of interference to house framing, plumbing, wiring, etc�
Figure 29: Straight through wall Installation.
2� Install a non-combustible hearth pad (where
necessary)�
3� Place the appliance 15” (37�5 cm) away from
the wall� If the stove is to be set on a hearth
pad, set the unit on it�
4� Locate the center of the exhaust pipe on
the stove� Extend that line to the wall�
Once you have located the center point on
the wall, refer to pellet vent manufacturer
installation instructions for correct hole size
and clearance to combustibles�
5� Install the wall thimble as per the instructions
written on the thimble� Maintain an effective
vapor barrier in accordance with local
building codes�
6� Install a length of 3” (76 mm) or 4” (101
mm) vent pipe into the wall thimble� The
pipe should install easily into the thimble�
7 Install the fresh air intake (see outsIde fresh
aIr ConneCtIon)
8� Connect the
exhaust vent pipe
to the exhaust pipe
on the stove� Seal
the connection with
high temperature
silicone�
9� Push the stove
straight back,
leaving a minimum
of 2” (5 cm)
clearance from the
back of the stove
to the wall� Seal
the vent pipe to
the thimble with
high temperature
silicone�
Figure 30: Venting to use with straight through wall Installation.
Non-combustible
floor protection.
Existing floor
(combustible)
6"
(15 cm)
2"
(5 cm)
Wall
thimble
Fresh air
intake
45°
elbow
12"
(30.5 cm)
Exhaust Tube
3" (75mm) or 4" (100mm) "PL" or "L" vent
Wall Thimble
45° Elbow with screen or
Termination Cap
Fresh Air Intake
High Temperature RTV
Silicone Required