The Ademco Contact ID Reporting format comprises a 4 digit subscriber
number, 1 digit event qualifier (“new” or “restore”), 3 digit event code, 2 digit
“00”, and 3 digit zone, contact ID, user, or system status number.
Ademco Contact ID
Reporting takes the following format:
CCCCQ EEEGG ZZZ
whale CC(% =
Customer (subscriber) ID
Q=
Event qualifier, where E = new event, and R = restore
EEE= Event code (3 hexadecimal digits, defined
in the table below)
GG =
Always 00.
ZZZ= Zone/contact ID number reporting the alarm, or user number for
open/close reporta. System status messages (AC Loss, Walk
Test, etc.) contain zeroes in the ZZZ location.
TABLE OF CONTACT ID EVENT CODES
Code I Definition
110 I Fira Alarm I
121 Duress
122 Silent Panic
123 Audible Panic
131
Perimeter Burglary
#E!!E==
302 Low System Battery
333 Expansion Module Fail
353 LR Radio Trouble
373 Fire Looo Trouble
Code I Definition
374 I
Exit Alarm I
\
380 Trouble (global)
381 Loss of Supervision -RF
383 Sensor Tamper
384 RF Transmitter Low Battery
401 O/C
By User
406 Cancel by User
407 Remote Arm/Disarm (Download)
408 Quick Arm
441 Armed STAY
570 Bypass
601 Test - Manually Triggered
602 Periodic Test