User manual

88
To be used as PTZ control
Enabling this function will transfer the output ports to PTZ control ports that will be used to control the
traditional PTZ and cannot be used as common output ports. For example, if it is a PT-811, all of the 8 output
points will be used as PTZ control ports, and can be operated with PT-908 relay output or PTZ control panel to
control traditional PTZ. Wiring of the PT-811 output ports is defined by the On/Off switches in the sequence
of up, down, left, right, zoom-in, zoom-out, Focus Near, and Focus Far.
Output Port Signal Type Setup
Individual names and signal formats can be assigned to output ports when they are used as common output
ports. Click on an output port in the
Select
area then set its name and the output signal type. There are four
signal types: OFF-to-On, On-to-off, positive pulse, and negative pulse. The default value is On-to-off. The
frequency and number of pulses may also be set. The default frequency is 1 second while the upper limit is
999 seconds. After the settings are complete, click
Save
to save the settings.
Input Port Mode Setup
Input ports can be given specific names and modes. Click on an input point in the
Select
area, then set up the
name and actions to respond to an input signal. The mode setup can function to trigger an action and turn the
alarm on or off.