Specifications
Manual # 016-0159-894 Rev H 01/07
55
2-Setting Up the
Controller Area
Calibrating the Pressure Transducer Using an Analog Gauge
1. Read the pressure on an analog gauge that is connected in line with the
pressure transducer.
2. Press the Pressure area box in the CAN Controller Status screen.
3. Using the screen keyboard, enter the pressure reading in the Pressure Sensor
field.
4. Press OK. Viper saves the information.
Entering a Setting with no Analog Gauge
1. Make sure that no pressure is applied to the transducer.
2. Enter a value of zero in the Pressure Sensor field.
3. Press OK.