RE_240-1CA20
Manual VIPA System 200V Chapter 3 Deployment
HB97E - CP - RE_240-1CA20 - Rev. 12/42 3-53
For the project engineering of the slave you only have to adjust the Modbus
parameters. A PLC application is not required for the source and desti-
nation data are delivered in the master telegram.
For the parameterization of the slave module open the sample project in
your hardware configurator. Select the module 240-1CA20. Via double-click
you reach the parameterization.
Dialog for address entry
Here you may set from which address on the
16Byte for in- and output are stored in the CPU.
Dialog for Modbus parameters
In this section of the parameterization you set
the Modbus parameters.
The following parameters must be identical for
all bus participants: baud rate, data bits, parity,
stop bits and flow control.
Enter a valid Modbus address for the slave into
Address.
Transfer the parameterization into the CPU of the slave system.
Slave project
engineering
Parameterization