RE_240-1CA20
Manual VIPA System 200V Chapter 3 Deployment
HB97E - CP - RE_240-1CA20 - Rev. 12/42 3-5
Project engineering
The address allocation and he parameterization of the directly plugged
System 200V modules happens by means of the Siemens SIMATIC
Manager in form of a virtual PROFIBUS system. You transfer your project
into the CPU serial via the MPI interface or directly via MMC.
For the project engineering of the CPU a thorough knowledge of the
SIMATIC Manager and the hardware configurator from Siemens is
required!
For the project engineering the following preconditions must be fulfilled:
• SIMATIC Manager from Siemens is installed at PC res. PG
• GSD files are included into hardware configurator from Siemens
• The project can be transferred into CPU (serial e.g. "Green Cable" or
MMC)
• Start the hardware configurator from Siemens with a new project and
insert a profile rail from the hardware catalog.
• At the first available slot you place the CPU 315-2DP (6ES7 315-2AF03
V1.2) from Siemens.
• If your CPU 21x has an integrated PROFIBUS-DP master, you may now
connect it to PROFIBUS and include your DP slaves.
• Create a PROFIBUS subnet (if not present yet).
• Add the system "VIPA_CPU21x" to the subnet. You will find this in the
hardware catalog under PROFIBUS DP > Additional field devices > IO >
VIPA_System_200V. Assign the PROFIBUS address 1 to this slave.
• In your configurator, place the CPU 21x, which you are using, always
on the 1. slot by taking it from the hardware catalog.
• Then you include your System 200V modules in the plugged sequence
and your CP 240 at the according place.
• If necessary parameterize your CP 240.
• Save your project.
General
Requirements
Hardware
configuration