Manual VIPA System 200V Chapter 3 Deployment
HB97E - CP - RE_240-1CA20 - Rev. 12/42 3-5
Project engineering
The address allocation and he parameterization of the directly plugged
System 200V modules happens by means of the Siemens SIMATIC
Manager in form of a virtual PROFIBUS system. You transfer your project
into the CPU serial via the MPI interface or directly via MMC.
For the project engineering of the CPU a thorough knowledge of the
SIMATIC Manager and the hardware configurator from Siemens is
required!
For the project engineering the following preconditions must be fulfilled:
SIMATIC Manager from Siemens is installed at PC res. PG
GSD files are included into hardware configurator from Siemens
The project can be transferred into CPU (serial e.g. "Green Cable" or
MMC)
Start the hardware configurator from Siemens with a new project and
insert a profile rail from the hardware catalog.
At the first available slot you place the CPU 315-2DP (6ES7 315-2AF03
V1.2) from Siemens.
If your CPU 21x has an integrated PROFIBUS-DP master, you may now
connect it to PROFIBUS and include your DP slaves.
Create a PROFIBUS subnet (if not present yet).
Add the system "VIPA_CPU21x" to the subnet. You will find this in the
hardware catalog under PROFIBUS DP > Additional field devices > IO >
VIPA_System_200V. Assign the PROFIBUS address 1 to this slave.
In your configurator, place the CPU 21x, which you are using, always
on the 1. slot by taking it from the hardware catalog.
Then you include your System 200V modules in the plugged sequence
and your CP 240 at the according place.
If necessary parameterize your CP 240.
Save your project.
General
Requirements
Hardware
configuration