RE_240-1CA20
Chapter 2 Hardware description Manual VIPA System 200V
2-6 HB97E - CP - RE_240-1CA20 - Rev. 12/42
Technical Data
Order number 240-1CA20
Type CP 240, RS485
Current consumption/power loss
Current consumption from backplane bus 150 mA
Power loss 0.75 W
Status information, alarms, diagnostics
Status display yes
Interrupts no
Process alarm no
Diagnostic interrupt no
Diagnostic functions no
Diagnostics information read-out possible
Supply voltage display yes
Group error display red LED
Channel error display none
Functionality Sub-D interfaces
Type -
Type of interface RS485
Connector Sub-D, 9-pin, female
Electrically isolated
9
MPI -
MP²I (MPI/RS232) -
DP master -
DP slave -
Point-to-point interface
9
Point-to-point communication
PtP communication
9
Interface isolated
9
RS232 interface -
RS422 interface -
RS485 interface
9
Connector Sub-D, 9-pin, female
Transmission speed, min. 150 bit/s
Transmission speed, max. 115.2 kbit/s
Cable length, max. 1200 m
Point-to-point protocol
ASCII protocol
9
STX/ETX protocol
9
3964(R) protocol
9
RK512 protocol
9
USS master protocol -
Modbus master protocol
9
Modbus slave protocol
9
Special protocols -
Datasizes
Input bytes 16
Output bytes 16
Parameter bytes 16
Diagnostic bytes 0
Housing
Material PPE
Mounting Profile rail 35 mm
Mechanical data
Dimensions (WxHxD) 25.4 x 76 x 78 mm