User`s manual

User's Manual
Arctic IEC-104 Gateway
Firmware Version 5.0.9 54 Document Version 1.5
Slave link address (IEC-101)
Table 26: IEC-101 slave link address
IEC-101 slave link address
Type Link address
Units N/A
Value range 1-65000
Note The link-level address of IEC-101 slave.
Link address field length
Defines the length of the IEC-101 link-level address field in bytes.
Table 27: IEC-101 slave link address field length
IEC-101 slave link address field length
Type Field length
Units Bytes
Value range 1, 2
Note The link-level address of IEC-101 slave.
Event poll interval
It defines the IEC-101 event polling interval in 0.1 second increments (class 1
or 2 poll).
Table 28: IEC-101 event poll interval
IEC-101 event poll interval
Type Interval
Units 0.1 seconds
Value range 1-65000
Note The events are polled only when the
IEC-104 connection is active.
Link test interval
It defines the IEC-101 link test interval in 0.1 second increments. Link test is
performed if there is no other activity.
Table 29: IEC-101 link test interval
IEC-101 link test interval
Type Interval
Units 0.1 seconds
Value range 1-65000
Note The link test is performed if there is no
other activity during defined interval.