7 IEC-104 application settings
The IEC-104 and IEC-101 protocols share the same ASDU level messaging
but differ on the link level. The IEC-104 is intended for packet-switched TCP/
IP communication whereas the IEC-101 is intended for serial communication.
By using the Arctic IEC-104 gateway, the IEC-101 slaves (e.g. RTUs) can
be connected to a IEC-104 master (e.g. SCADA). The Arctic requests event
from the IEC-101 slave locally and sends them to the IEC-104 master. This
eliminates the need to continuously poll the data remotely and therefore
reduces the communication costs on pay-per-use GPRS network. This
approach also eliminates the IEC-101 parameter adjutancy problems caused
by variable round-trip delays on GPRS networks and makes the information
exchange faster and more reliable.
Figure 34. IEC-104 Application Settings
7.1 General settings
IEC-104 gateway enabled
Enables or disables IEC-104 to IEC-101 gateway functionality.
Table 6: IEC-104 gateway enabled
IEC-104 gateway enabled
Type Boolean
Units N/A
Value range No, Yes