Firmware Version 5.0.9 40 Document Version 1.5
SNMP agent (SNMP Set/Get) – Set SNMP agent enabled or disabled.
Read only SNMP community – read only community string.
Read and write SNMP community – rw snmp community
Server port (standard=161) – Agent listen port (UDP)
Bind to interface – The interface is used as source address.
5.5 Application Menu
Application menu contains the serial device server application. With this
application, serial devices can be connected to the Arctic Gateway and used
over the TCP/IP network.
Serial GW
Serial gateway can be enabled from this menu. When enabled in “Server”
operation mode, TCP/IP (or UDP) connections can be made to the Arctic
(Local Server Port). When Serial GW is in “Client” operation mode, Arctic
Gateway sends the received serial data via TCP/IP to host (Remote IP
Address or host) to remote host (Remote Port).
IEC-104 serial device can be connected to RS1 or RS2 port. The RS2 serial
port can be used either as an RS-232 or an RS-485 type port (IEC-104).
To enable serial gateway functionality on RS1 the console (RS1) port, the
console switch has to be set to “0”.
Figure 28. Serial Gateway Settings
Arctic IEC-104 Gateway specific settings are described in the chapter IEC-104
application settings on page 46.
For example, a device connected to an Arctic GW application (when in server
operation mode) serial port could be accessed with telnet utility as follows:
telnet <Arctic IP Address> 2404