Specifications

74 / 80
When configuring the IEC-104 for GPRS connection, one can start with the following values:
IEC t0 (connection establishment timeout, SCADA only) > 30 secs
IEC t1 (ack rx timeout) = 60 secs
IEC t2 (ack tx timeout) = 20 secs
IEC t3 (link test interval) = 200…600 secs,
SCADA should have approx. 30sec less than arctic
IEC k (tx window size) = 12
IEC w (rx window size) = 8
Any completion/control/GI timeout > 60 secs
See Arctic IEC-104 Gateway’s User’s manual for more settings.
20.2. Arctic Modbus Gateway
The Arctic Modbus Gateway offers the following key properties:
Supports Modbus RTU and Modbus ASCII serial protocols
Supports ModbusTCP, ModbusRTU over TCP, ModbusRTU over UDP, Modbus
ASCII over TCP and Modbus ASCII over UDP network protocols
Can generate and filter out gateway exceptions
Can route traffic on network based on Modbus addressing enabling intelligent use of
network resources
Makes automatic connection management
Enables multiple server sessions over network
Offers unlimited amount of Masters on serial or Network side
Offers 30 routes over network to slaves.
See the Arctic Modbus Gateway specific settings from Arctic Modbus Gateway, Configuration
Manual.
21. Appendix E: Troubleshooting
Troubleshooting the solution may sometimes be a difficult task. It is a good practice to divide the
solution into smaller subparts, e.g. LAN and WAN connectivity, VPN tunneling, routing, serial
connection and so on.
21.1. Troubleshooting principles
Define the environment
– how it should work?
Technologies, products, protocols, network design
Gather the symptoms
– how you see the problem?
What is not working, where you can see it?
Isolate the root cause
– analyze, rule out
Follow good troubleshooting practices
Create a solution
– focus for permanent solution
Permanent solution rather than a quick fix