Installation Sheet

3
cabinet temperature, higher ambient temperature and less insulation will
cause a reduction in capacity and may not maintain a temperature of 55°F.
The ambient temperatures for WM-1500SLIM should not be higher than 78°F
or lower than 50°F.
Mounting brackets, screws, gaskets and other seal materials are not included.
Do not install any ducts onto the supply, return, intake and exhaust.
Because of potential safety hazards under certain conditions, we strongly
recommend against the use of an extension cord. However, if you still elect to
use an extension cord, it is absolutely necessary that it be a UL LISTED 3-
wire grounding type appliance extension cord having a 3-blade grounding
plug and a 3-slot receptacle that will plug into the appliance. The marked
rating of the extension cord should be 115 V, 15 A.
1. Cabinet Location
Place the wine cabinet in a properly ventilated location. Otherwise, heat
exhausted by the cooling unit will build up and it will not operate properly.
The exhaust area must not be in an enclosed space and must be ventilated.
The ambient temperatures should not be higher than 78°F for a WM-
1500SLIM or WM-1500SLIM-TE unit.
1) Rear Exhaust Cabinet Location
Leave min 6 “clearance from the rear to the wall.
Leave min 12” clearance from the top to the ceiling.
Leave min 6” clearance from the left and right sides.
2) Front Exhaust Cabinet Location
Leave min 6” clearance from the front if left and right sides unobstructed.
Or, leave min 36” clearance from the front if left and right sides obstructed
3) Top Exhaust Cabinet Location
Leave min 12” from the top to the ceiling.
Leave min 2 “clearance from the rear to the wall.
Leave min 2” clearance from the left and right sides.
4) Side Exhaust Cabinet Location
Leave min 6 “clearance from the left or right side to the wall.
Leave min 12” clearance from the top to the ceiling.
2. Cooling Unit Installation
The cooling unit produces cooling supplied into the cabinet, meanwhile it also
generates heat that must be exhausted outside the cabinet. So the cold-air
supply with return-air intake and hot-air exhaust with ambient-air side must be
separated and sealed. Foam tape gasket may be used to seal them. The