User manual
       - 1 -
2. Evaporator Unit 
•  The WM-15SFC evaporator unit is installed for ceiling mount with the air 
supply towards horizontally and air return on the bottom. 
•  The WM-19SFC evaporator unit is installed for wall mount with the air 
supply towards top and air return on the sides. 
•  Supply and return air flow from the evaporator unit shall be unobstructed 
for at least 1 foot. 
• There is a gravity drain line so that it can not be installed above the 
evaporator unit. Otherwise a condensation pump must be used. 
3.  Refrigeration Piping and Charging 
NOTES: ALWAYS USE THE SUPERHEAT AND SUBCOOLING, 
PRESSURE READINGS TO CHARGE REFRIGERANT PROPERLY, THE 
LISTED CHARGES ARE FOR REFERENCE ONLY. 
•  The installation order starts from condensing unit (including the receiver), 
liquid line filter-drier, moisture-liquid indicator (sight glass), liquid line, 
evaporator unit (including liquid line solenoid valve and thermostatic 
expansion valve or automatic expansion valve), returning to suction line 
and condensing unit. 
•  The subcooling at the condensing unit shall be around 10°F. The charge 
may be complete when there are no more bubbles forming in the sight 
glass. 
•  The evaporator superheat is set around 8-10 °F for a 10 °F TD system at 
factory. 
•  Low side pressure: around 33 psig 
•  High side pressure: 130 -150 psig at 75 -90 °F ambient temperatures 
The line sizes and refrigerant charges are listed as follows. 
MODEL 
REFRIGERATION 
LINES 
LIQUID 
LINE 
SUCTION 
LINE 
DRAIN 
LINE 
CHARGE 
VINO-1500SS  < 50 FT 
1/4" 
OD 
3/8” OD  1/2” OD 
R134a/ 
15 OZ 
VINO-1900SS  < 50 FT 
1/4" 
OD 
3/8” OD  3/8” OD 
R134a/ 
15 OZ 
4.  Pressure, Superheat and Subcooling Readings 
NOTES: THE SERVICE VALVES MUST BE IN THE MIDDLE POSITIONS TO 
READ PROPERLY. 
Complaint Possible Causes 
a.  High suction pressure and low head pressure 
b.  High suction pressure and low head pressure 
 Low superheat and low subcooling 
a.  Compressor may be bad 
b. Expansion valve opened, too 
much oil 