Use and Care Manual
- 11 -
3) Press up/down keys / to scroll to the required parameter within 10 sec.
4) Press the “SET” key to display its value.
5) Use up/down keys to change its value within 10 sec.
6) Press “SET” to store the new value.
7) To exit: Press SET + or wait 15sec without pressing a key.
PARAMETER
DESCRIPTION
DEFAULT VALUE
Set
set-point (°)
55
Hy
temperature regulation differential (°)
4
AC
anti-short cycle delay (min)
10
Con
compress on with probe faulty (min)
15
CoF
compress off with probe faulty (min)
30
CF
temperature unit (°F/ °C)
F: Fahrenheit
rES
display resolution
in: integer
dLy
temperature display delay (min)
1
ot
probe calibration (°)
0
US
maximum set-point (°)
65
LS
minimum set-point (°)
50
idF
defrost cycle interval time (hour)
12
MdF
defrost cycle endurance time (min)
30
ALC
temperature alarm type
rE: relative to set-point
ALU
high temperature alarm (°)
10
ALL
low temperature alarm (°)
10
AFH
alarm recovery differential (°)
5
ALd
temperature alarm delay (min)
60
dAO
temperature alarm delay on startup (hr)
23
SAA
cellar heater set-point (°)
40
SHy
cellar heater regulation differential (°)
4
FnC
fan operating mode
C-n: on with compressor & off during defrost
Fon
fan on with compressor off (min)
0
FoF
fan off with compressor off (min)
15
NOTE: Depending on the unit, not all parameters are used.