Technical data
17
Propylene glycol/water solutions are designed to be installed on systems
supplied by potable water supplies. Local authorities should be consulted
prior to draining system to storm sewers or to natural drainage areas. In
the main drain line between the valve and Easy Riser
TM
Check Valves
inlet, a tee is provided on the check valve trim with a 1” NPT connection
for supply and maintenance of the antifreeze solution to the system above
the primary Easy Riser
TM
Check Valve.
5.1.3 Reclaim Tank
An atmospheric storage tank is to be installed for
the system(s) that is of adequate capacity of the
largest system volume installed. The tank shall be
utilized as a reclaim tank for the propylene glycol
solution in the system piping when the system(s)
are drained for system service and for discharge
of propylene glycol solution if system pressure
exceeds 175 PSI (1 207 kPa) at the sprinklers.
The ball valve must be shut before the switch on
the CS-1 Panel is placed in Automatic Mode.
5.1.4 Automatic Pressure Control System
A means of relieving system pressure due to pressure buildup can be
provided through a specialized pressure switch and solenoid valve on the
downstream side of the primary check valve. See data page 47 a-b.
Storage areas that are expected to fluctuate more than 10 degrees from
nominal temperature will experience increased pressure in the system
Exam
p
le