Specifications

TECHNICAL SUPPORT 1 800 908 0884
26
Fail Safe:
By removing the wire-jumper plug
from the “Fail Safe/Secure” connector:
The gate can be move manually with
relative low amount of force.
Fail Secure:
By inserting the wire-jumper plug into the
“Fail Safe/Secure” connector:
The gate can still be move by hand with
relative high amount of force.
In case of faulty operation or power failure,
remove the cover, locate the Reset Switch
and turn it to the “OFF” position. The gate
can now be pushed manually.
At the end of operations, turn the switch to the
“RESET” position to resume normal operation.
SPECIAL FEATURESSPECIAL FEATURES
Hold Open
Timer
p
Open
Hold Open
Timer
S
Open
Limit
30sec
60secoff
1sec
EN LEFT
Fail Safe/Secure
1
2
The gate operator contains a unique design that
allows the user to move the gate manually in case
of power failure.
There are three levels of force required to move
the gate manually.
1
2
TECHNICAL SUPPORT 949-753-1279
Fail Safe/Fail Secure Operation
Hold Open Timer
Connection Locations
The Hold Open Timer function holds the gate at
the open position for a predetermined amount
of time, prior to closing automatically.
Set the Timer to the desired time, from 1 to
60 seconds.
If this feature is not needed, turn the Trim
Pot clockwise to the “off” position.
Note: The Hold Open Timer affects the “radio
receiver command” and the sequence of
operation for the gate (see page 23).