Installation Manual

50
Y & S Plan system (2 pipes) (Hydraulic cylinder Flow and Return connections
capped off at the boiler)
Connect the required permanent live
supply to plug 40 as combination boiler.
An external independent twin channel
remote timer is used.
The Vitotronic HC2 integral timer must
be set to constant operation.
The switched live supply from Y & S
plan electrical configurations (that con-
trols the pump and boiler) is connected
to plug 96 terminal 1.
The Viessmann low voltage DHW
sensor must not be fitted, this means
the 3 port valve integral to the boiler
will remain open correctly.
Vitotrol 100 UTA/D external controls are
not compatible.
Control heating & DHW via external
independent timer.
Heating only system (2 pipes)
Connect the required permanent live
supply to plug 40 as previous page.
Connect room thermostat to plug 96 as
combination boiler.
The Viessmann low voltage DHW
sensor must not be fitted, this means
the 3 port valve integral to the boiler
will remain open correctly.
Time heating via integral Vitotronic HC2
control.
A Vitotrol 100 UTA/D can be connected
to plug 96, however the integral
Vitotronic HC2 7 day controller would
require the central heating to be set to
permanently on, please refer to user
guide.