Installation Manual

49
5350 485 GB 08/2007
Coding
Calling up code 2
Note
On weather-compensated control units,
codes are displayed as plain text.
Codes that are irrelevant due to the
system equipment level or the setting
of other codes will not be displayed.
Press the following keys:
Switch on the boiler using button page 29 and button page 31.
1.
simultaneously for approx. 2 s.+
/
8.
simultaneously for approx. 1 s;
code 2 is terminated.
+
2.
to confirm
OK
OK
3.
for coding address 53; the
address flashes
+
_
/
5.
for the selected value 3, this will
change the code to function relay
external cylinder loading pump
+
_
/
7.
for the selection of further
addresses
+
_
4.
to confirm; the value flashes
OK
6.
to confirm; the display briefly
shows “accepted” (for weather-
compensated control units); the
address flashes again.
F A