Condensate connection
Routing
The condensate pipe can terminate into any one of the following areas.
It is always best practice to terminate the condensate pipe via an internal waste system.
• The pipe run should take the shortest practical route with a downward slope of at least
2.5 ° (4.5 mm/m)
• The external pipework should be insulated to prevent freezing
• The pipework should terminate as close as possible to the ground or drain, whilst still
allowing the condensate to discharge safely
• The condensate pipe must be of non corrosive material, preferably plastic
Note: ferrous materials or copper must not be used
Ø 22mm plastic condensate pipe
A
A
Connect the condensate drain and discharge
correctly as detailed overleaf.