Flue terminal position (cont.)
Vertical flue systems
Position
C
D
E
F
G
H
I
J
K
L
M
N
200mm
200mm
150mm
300mm
300mm
600mm
1200mm
1200mm
1500mm
300mm
300mm
200mm
Below eaves
Below a balcony
From vertical drain or soil pipes
From internal and external corners
Above adjacent ground or balcony level/roof
From a surface facing the terminal
Facing terminals
From opening door/window in carport into dwelling
Vertically from a terminal on same wall
Horizontally from a terminal on same wall
Adjacent to opening
Below carport/roof
Minimum Spacing