Technical Data Manual Model Nos. and pricing : See Price List VITORONDr 100 Hot water heating boiler 91 to 245 MBH 27 to 72 kW Product may not be exactly as illustrated.
Product Information Vitorond 100, VR1 Technical Data Vitorond 100 A genuine triple-pass boiler of cast iron sectional design. The high-quality construction and innovative oil heating technology of this boiler provides a high level of operational reliability, high-efficiency operation and reduced emissions. Benefits at a glance: Get the most out of your fuel dollar! Maximum heat extraction with triple-pass design. A.F.U.E.: up to 86.9%.
Vitorond 100, VR1 Technical Data Product Information Cutaway Section A Special return water flow control injector B Eutectoplex heat exchanger surface of special homogeneous gray cast iron C Vitotronic 100 - indoor/outdoor digital boiler and heating system control D Oil burner E Third pass F Combustion chamber*1 5583 772 - 03 *1 Stainless steel combustion chamber insert not shown. Boiler/burner and controls combination may not be exactly as illustrated.
Specifications Vitorond 100, VR1 Technical Data Boiler Model No. CSA Input *1 CSA Output Net AHRI rating A.F.U.E.
Specifications Vitorond 100, VR1 Technical Data Vitorond 100 Vitorond 100 with Aquastat or Hydrostat * See page 4 Legend BD Boiler Drain BTS Boiler Temperature Sensor BWR Boiler Water Return BWS Boiler Water Supply FGC Flue Gas Collar SR Safety Return SS Safety Supply BHL Boiler High Limit (with outdoor reset module) A Boiler Stand B Beckett or Riello Burner Dimensions Boiler Model a b c d e f g h k VR1 in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in.
Specifications Vitorond 100, VR1 Technical Data Clearances Minimum Clearances to Combustibles Standard installation Boiler Model VR1 Rear inches (mm) inches (mm) inches (mm) Sides Flue -22 -27 -33 -40 -50 -63 6 (150) 0 (0) 9 (230) 6 (150) 0 (0) 9 (230) 6 (150) 0 (0) 9 (230) 6 (150) 0 (0) 9 (230) 6 (150) 0 (0) 9 (230) 6 (150) 0 (0) 9 (230) Combustibles Floor Alcove installation VR1 inches (mm) inches (mm) inches (mm) inches (mm) Sides Flue Top*2 Floor *1 Front service clearance.
Specifications Vitorond 100, VR1 Technical Data Dimensions Beckett burner (chimney and direct vent*1 application) Boiler Model Model No. Burner model Beckett Fuel type oil Pump pressure psig (kPa) Oil nozzle VR1-22* VR1-27* VR1-33* VR1-40 VR1-50 VR1-63 NX-VI 701 NX-VI 702 NX-VI 703 NX-VI 704 AFG-VI 801 AFG-VI 801 175 (1207) 175 (1207) No. 2 fuel oil 175 (1207) 175 (1207) Danfoss n.a. Delavan 0.50x60°B Hago 0.50x60°B Oil nozzle flow rate GPH@psig 175 (1207) 175 (1207) 0.
Specifications Dimensions Vitorond 100, VR1 Technical Data (continued) Riello burner (direct vent application) Boiler Model Model No. Burner model Riello 40 Series Fuel type oil Pump pressure psig (kPa) Oil nozzle VR1-22 BF3 VR1-27*1 VR1-33 BF3*1 BF5 No. 2 fuel oil 175 (1207) 175 (1207) 140 (965) Danfoss n.a. n.a. n.a. Delavan 0.50x60°SS 0.60x60°W*3 0.85x60°W*2 n.a. n.a. n.a. Hago Oil nozzle flow rate GPH@psig 0.65@175 0.75@175 1.
Vitorond 100, VR1 Technical Data Installation System Design Considerations Chimney For proper operation of the Vitorond boiler, all products of combustion must be safely vented to the outdoors, while ensuring that flue gases do not cool prematurely. It is critical that the chimney system be properly designed to handle the flue gas temperatures which the Vitorond boiler produces.
Installation System Design Considerations Vitorond 100, VR1 Technical Data (continued) Water quality Treatment for boiler feed water should be considered in areas of known problems, such as where a high mineral content and hardness exist. In areas where freezing might occur, an antifreeze may be added to the system water to protect the system. Please adhere to the specifications given by the antifreeze manufacturer. Do not use automotive silicate based antifreeze.
Installation Vitorond 100, VR1 Technical Data System Design Considerations Waterside flow (continued) Flow rates The relationship between boiler flow rate and temperature rise is according to the formula: Boiler output (Btu/h) = 500 x flow (USGPM) x Rise (°F) The following chart lists typical flow rates for the Vitorond boiler: Boiler Model VR1 -22 -27 -33 20° F rise USGPM 30° F rise USGPM 8 9.2 12.2 5.3 6.1 8.1 Boiler Model VR1 -40 -50 -63 20° F rise USGPM 14 17.2 21.
Installation Vitorond 100, VR1 Technical Data Installation Examples - Hydrostat Boiler in a heating/cooling application Cooling season starts: close valve v1 and open valve v2 Heating season starts: close valve v2 and open valve v1 Legend A Heating/Cooling unit B Spring-loaded flow check valve C Circulation pump D Automatic air vent, E Pressure relief valve F Hydrostat 3250-Plus (with low water cut-off) G Water chiller H Expansion tank IMPORTANT We strongly suggest that the valves be labelled “v1” and v
Installation Vitorond 100, VR1 Technical Data Installation Examples - Vitotronic Without mixing valve e.g. with Vitotronic 100, Model KW10B Legend A Heating circuit B Spring-loaded flow check valve C Circulation pump D Automatic air vent, (field supplied), pressure relief valve, and temperature pressure gage E Expansion tank F Low water cut-off (if required) 5583 772 - 03 Without mixing valve and with DHW e.g.
Installation Installation Examples - Vitotronic Vitorond 100, VR1 Technical Data (continued) With one low-temperature circuit with 4-way mixing valve, and with domestic hot water production. e.g.
Installation Vitorond 100, VR1 Technical Data Installation Examples - Vitotronic (continued) With one low-temperature circuit with 4-way mixing valve, one high temperature circuit, and with domestic hot water production. e.g.
5583 772 - 03 Technical information subject to change without notice. Printed on environmentally friendly (recycled and recyclable) paper.