Technical data

Vitorond 100, VR1-22 to -33 Installation and Service
5583 571 - 01
54
WARNING
Ensure that warning concerning fiberglass wool and
ceramic fiber materials on page 3 has been read and
understood before handling insulation.
WARNING
NEVER ADJUST BURNER BY EYE.
WARNING
Always keep the manual fuel supply valve shut off if the
burner is shut down for an extended period of time.
WARNING
Never burn garbage or paper in the unit, and never leave
combustible material around it.
Necessary Tools
Testing/analysis equipment
H Calibrated flue gas analyzer
Cleaning supplies
H Hand brush
H Rags
H Vacuum cleaning
Possible replacement parts
H Rope sealant for combustion chamber door
H Refractory for combustion chamber door
IMPORTANT
Use only calibrated equipment.
Service Procedure
Shut-down heating system
1. Ensure main power supply to equipment, the heating
system, and all external controls has been
deactivated. Take precautions in both instances
to avoid accidental activation.
2. Close main oil supply valve near burner and near tank.
Open combustion chamber door
1. Disconnect power supply.
2. Remove front panel A by lifting panel up and out.
3. Remove two bolts B of combustion chamber door C
and open. Continued on following page.
4. Remove turbulators, if applicable. See page 59 for
details.
5. Remove combustion chamber insert (if applicable).
Service