Technical data
Vitorond 100, VR1-22 to -33 Installation and Service
5583 571 - 01
48
Start-up
Riello Burner Calibration
IMPORTANT
Boiler Model No. VR1-22 VR1-27 VR1-33
Burner model Riello 40 Series F3 F3*1 F5
Fuel type oil No. 2 fuel oil No. 2 fuel oil No. 2 fuel oil
Pump pressure psig 175 175 175
Oil nozzle Danfoss 0.50x60°xAS 0.60x60°xAS*3 0.75x60°xAS
Delavan 0.50x60°xSS 0.60x60°xW 0.75x60°xA
0.75x60°xW*2
Hago 0.50x60°xSS*2 0.60x60°xES n.a.
Oil nozzle flow rate GPH@psig 0.65@175 0.75@175 1.00@175
Air tube length inches
mm
7
178
7
178
6
5
/
16
160
Air tube insertion inches
mm
4f
118
4f
118
4¼
108
Air tube combination 0.0 2.0 0.8
Head type 3.1 3.4 2.9
*1 For VR1-27 boiler, replace installed nozzle with nozzle
packaged with Riello burner.
*2 Factory-installed nozzle.
*3 Nozzles must be installed by installer.
Note: Riello oil burners are factory set for Vitorond 100,
VR1-22, and -33 boilers and should only require
minor adjustments. Install appropriate nozzle and
set the burner for model VR1-27.