Installation Instructions

29
9. Open the gas shut-off valve and start
the appliance.
Danger
Gas escaping from the test
nipple leads to a risk of explo-
sion.
Check gas tightness at test
nipple
A
.
Note
The maximum pressure drop
between the gas shut-off valve and
test nipple
A
at the gas train is
0.5 mbar.
Supply pressure (flow pressure) Action
for natural gas for LPG
below 17.4 mbar below 25 mbar Do not start the boiler. Notify your gas
supply utility or LPG supplier.
17.4 to 25 mbar 25 to 47 mbar Start the boiler.
above 25 mbar above 47 mbar Install a separate gas pressure governor
upstream of the system and regulate the
pre-charge pressure to 20 mbar for natu-
ral gas or 37 mbar for LPG. Notify your
gas supply utility or LPG supplier.
Matching the burner output to the flue system
To match the burner output to the sys-
tem's flue pipe length, a correction factor
can be set.
1. Turn ON/OFF switch ON.
r
2. Turn both rotary selectors "tw" and
"
tr
" simultaneously into their
respective central positions.
"SERV" appears on the display.
3. Refer to the following table for the
correction factor required for the con-
nected flue system.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5609 059 GB
Service