Installation Instructions
28
Checking the static and supply pressure
Danger
CO build-up as a result of incor-
rect burner adjustment can have
serious health implications.
Carry out a CO test before and
after work on gas appliances.
Operation with LPG
Flush the LPG tank twice during com-
missioning or replacement. Purge the
tank and gas supply line thoroughly after
flushing.
A
1. Close the gas shut-off valve.
2.
Undo screw A inside test nipple
"IN" on the gas train but do not
remove it, and connect the pressure
gauge.
3. Open the gas shut-off valve.
4. Check the static pressure.
Set value: max. 57.5 mbar
5. Start the boiler.
Note
During commissioning, the boiler can
enter a fault state because of airlocks
in the gas line. After approx. 5 s press
Reset to reset the burner.
6. Check the supply (flow) pressure.
Set value:
■ Natural gas: 20 mbar
■ LPG: 37 mbar
Note
Use a suitable measuring device with
a resolution of at least 0.1 mbar to
check the supply pressure.
7. Record the actual values in the report
on page.
Take the action shown in the follow-
ing table.
8. Shut down the boiler, close the gas
shut-off valve, remove the pressure
gauge and close test nipple
A
with
the screw.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5609 059 GB