Installation Instructions

24
Filling the heating system
!
Please note
Unsuitable fill water increases
the level of deposits and corro-
sion and may lead to boiler dam-
age.
Thoroughly flush the entire
heating system prior to filling it.
Only use fill water of potable
quality.
Soften fill water harder than
300 ppm.
An antifreeze additive suitable
for heating systems can be
added to the fill water.
1. Close the gas shut-off valve.
2. Switch ON the power supply.
rr
3. Turn rotary selector "rt" anti-clock-
wise for less than 2 s and then clock-
wise back into the control range.
"SERV", "
r
" and "
w
" will appear
on the display. Filling has been acti-
vated.
This function will end automatically
after 20 min or after the ON/OFF
switch has been turned off.
Commissioning, inspection, maintenance
Further details regarding the individual steps
5609 059 GB